4. The recovered refrigerant shall be loaded in the appropriate storage tanks, attached with a
transporting instruction, and returned to the refrigerant manufacturer. Don’t mix refrigerant in
recovery equipment, especially a storage tank.
5. The space loading R32 refrigeration can’t be enclosed in the process of transportation. Take anti
electrostatic measures if necessary in transportation. In the process of transport, loading and
unloading, necessary protective measures must be taken to protect the air conditioner to ensure
that the air conditioner is not damaged.
6. When removing the compressor or clearing the compressor oil, make sure the compressor
is pumped to an appropriate level to ensure that there is no residual R32 refrigerants in the
lubricating oil. The vacuum pumping should be carried out before the compressor is returned to the
supplier. Ensure the safety when discharging oil from the system.Installation instructions
11
Maintenance Notice