Split type wall mounted air-conditioner / Owner’s Manual
39 / 220 EN
825 (880) × 655 × 310
540
335
900 (950) × 700 × 350
630
350
900 (950) × 795 × 330
535
350
970 (1044) × 803 × 395
675
409
9.2 Install the connection pipe
Connect the Outdoor Unit with Connecting Pipe: Aim the counter-bore of the connecting pipe at the
stop valve, and tighten the Taper nut with fingers. Then tighten the Taper nut with a torque wrench.
Taper nut
Stop valve
Connecting
pipe
liquid side pipe
Gas side pipe
Spanner
•
When prolonging the piping, extra amount of refrigerant must be added so that the operation and
performance of the air conditioner will not be compromised.
Piping length
Amount of refrigerant to be added
Amount of refrigerant for the unit
≤ 5 M
Not needed
5-15 M
CC ≤ 12000 Btu
16 g/m
≤ 1 kg
CC ≥ 18000 Btu
24 g/m
≤ 2 kg
C
Note:
1. This table is for reference only.
2. The joints shall not be reused, unless after re-flaring the pipe.
3. After installation, check the stop valve cover whether be fixed effectively.
9
Install outdoor unit
Содержание BEVPA 090
Страница 54: ...Manufactured by Arcelik A S Karaagac Cd No 2 6 34445 Sutluce Beyoglu Istanbul Turkey 19 11 Rev 01 ...
Страница 106: ...19 11 Rev 01 Prodotto da Arcelik A S Karaagac Cd No 2 6 34445 Sutluce Beyoglu Istanbul Turchia ...
Страница 161: ...Fabricado por Arcelik A S Karaagac Cd No 2 6 34445 Sutluce Beyoglu Estambul Turquía 19 11 Rev 01 ...
Страница 217: ...Fabricado por Arcelik A S Karaagac Cd No 2 6 34445 Sutluce Beyoglu Istambul Turquia 19 11 Rev 01 ...
Страница 218: ......
Страница 219: ......
Страница 220: ...www beko com ...