Commissioning
Code Function
Implementation
Application/evaluation
A
The EtherCAT Master's
diagnostic information
updated acyclically (yellow) or
provided acyclically (green).
At least the DevState is to be
evaluated for the most recent cycle
in the PLC.
The EtherCAT Master's diagnostic
information offers many more
possibilities than are treated in the
EtherCAT System Documentation.
A few keywords:
• CoE in the Master for
communication with/through
the Slaves
• Functions from
TcEtherCAT.lib
• Perform an OnlineScan
B
In the example chosen (EL3102)
the EL3102 comprises two
analogue input channels that
transmit a single function status
for the most recent cycle.
Status
• the bit significations
may be found in the
device documentation
• other devices may
supply more
information, or none
that is typical of a
slave
In order for the higher-level PLC
task (or corresponding control
applications) to be able to rely on
correct data, the function status
must be evaluated there. Such
information is therefore provided
with the process data for the most
recent cycle.
C
For every EtherCAT Slave that
has cyclic process data, the
Master displays, using what is
known as a WorkingCounter,
whether the slave is participating
successfully and without error in
the cyclic exchange of process
data. This important, elementary
information is therefore provided
for the most recent cycle in the
System Manager
1. at the EtherCAT Slave,
and, with identical contents
2. as a collective variable at
the EtherCAT Master (see
Point A)
for linking.
WcState (Working Counter)
0: valid real-time
communication in the last
cycle
1: invalid real-time
communication
This may possibly have
effects on the process data
of other Slaves that are
located in the same
SyncUnit
In order for the higher-level PLC
task (or corresponding control
applications) to be able to rely on
correct data, the communication
status of the EtherCAT Slave must
be evaluated there. Such
information is therefore provided
with the process data for the most
recent cycle.
EL72x1-0010
71
Version: 2.0
Содержание EL7201-0010
Страница 2: ......
Страница 12: ...Product overview 3 Product overview 3 1 Introduction Fig 8 EL7201 Fig 9 EL7211 EL72x1 0010 12 Version 2 0 ...
Страница 47: ...Commissioning Fig 42 TCP IP setting for the Ethernet port EL72x1 0010 47 Version 2 0 ...
Страница 57: ...Commissioning Fig 61 EtherCAT terminal in the TwinCAT tree EL72x1 0010 57 Version 2 0 ...
Страница 119: ...Commissioning Fig 148 Touch Probe inputs EL72x1 0010 119 Version 2 0 ...
Страница 138: ...Commissioning Fig 168 Process Data tab SM2 EL72x1 0010 default EL72x1 0010 138 Version 2 0 ...
Страница 142: ...Commissioning Fig 171 Process Data tab SM2 EL72x1 0010 default EL72x1 0010 142 Version 2 0 ...