Commissioning
EL6201
117
Version: 2.2
Fig. 154: No slave detected in the AS-i System Overview
• Now connect the first slave with the AS-i fieldbus line. The slave is automatically addressed with "1A",
as shown below (Fig.
The first slave connected is allocated address "1A"
). The address is now
permanently implemented in the slave.
• Now connect further slaves with the AS-i fieldbus line. The slaves are allocated addresses "2A" and
"3A", as shown below.
Fig. 155: The first slave connected is allocated address "1A"