Commissioning
EL6201
118
Version: 2.2
Fig. 156: The second slave connected is allocated address "2A"
Note
Problems during project planning through AS-i "Periphery Fault"
During project planning of a new AS-i slave, an AS-i "Periphery Fault" may put automatic
project planning into an undefined state, as indicated by flashing in the project planning
overview; see Fig.
Undefined state of a slave to be projected
.
Remedy:
Click on the grey button "AS-i Data Exc INACTIVE", which switches to green "AS-i Data
Exc ACTIVE" (see Fig.). The slaves should then show a stable state "Detected and acti-
vated" (blue).