Product overview
EL6201
13
Version: 2.2
2.2
Technical data
Technical data
EL6201-0000
AS-Interface channels
1
Number of slaves
up to 31 in V 2.0; up to 62 in V 2.11, V 3.0
AS-Interface versions
V 2.0, V 2.11, V 3.0 (Rev. 4)
Slave types
Standard: digital and analog,
extended:
Type 1 (CTT1): S-7.3, S-7.4,
Type 2 (CTT2): S-7.5.5, S-7.A.5, S-B.A.5,
Type 3 (CTT3): S-7.A.7, S-7.A.A,
Type 4 (CTT4): S-7.A.8, S-7.A.9,
Type 5 (CTT5): S-6.0,
Safety at work: S-0.B, S-7.B
Diagnostics
power failure, slave failure, parameterization fault
AS-Interface address assignment
via configuration or automatic
Cycle time
max. 5 ms (with 31 or 62 slaves)
Connection
2 lines via spring force technology
Data transfer rates
167 kbit/s
Distributed clocks
-
Power contacts
no
Electrical isolation
500 V (AS-Interface/E-bus)
Supply voltage for electronics
via the E-bus
Current consumption
120 mA (E-Bus), typ. 40 mA/max. 60 mA (AS-Interface)
Configuration
via TwinCAT System Manager
Dimensions (W x H x D)
approx. 27 mm x 100 mm x 70 mm (width aligned: 24
mm)
Weight
approx. 55 g
Assembly [
}
27]
on 35 mm mounting rail conforms to EN 60715
Operating temperature
0°C ... +55°C
Storage temperature
-25°C ... +85°C
Relative humidity
95 % no condensation
Vibration/shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27,
see also
installation instructions [
}
30]
for enhanced
mechanical load capacity
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protect. class / installation pos.
IP20 /
see note [
}
34]
!
AS-Interface certificate
yes, cert. no. 97701
Approvals
CE