Commissioning
EL6201
140
Version: 2.2
Index App0 ASI Diag Data Slave (for 00 ≤ pp ≤ 1F; slave 0 to slave 31)
Index (hex) Name
Meaning
Data type
Flags
Default
App0:0C
Physical Fault
Counter (B-Slave)
Counter that increments if a response from the respec-
tive AS-i slave had a start bit, stop bit or parity bit error
UINT16
RO
0x0000 (0
dec
)
App0:0D
Timeout Counter (B-
Slave)
Counter that increments if the respective AS-i slave did
not respond
UINT16
RO
0x0000 (0
dec
)
App0:0E
Response Counter
(B-Slave)
Counter that increments if the respective AS-i slave re-
sponded correctly
UINT16
RO
0x0000 (0
dec
)
App0:0F
Leave Data-Exchange
Counter (B-Slave)
Counter that increments if the respective AS-i slave has
been deleted from the LAS, i.e. it did not respond (or cor-
rectly respond) three times in succession
UINT16
RO
0x0000 (0
dec
)
App0:10
Data-Exchange Failed
Counter (B-Slave)
Counter that increments if the respective AS-i slave did
not respond (or correctly respond) to a data exchange
telegram
UINT16
RO
0x0000 (0
dec
)
App0:11
Timeout Statistics (B-
Slave)
Timeouts per telegram in percent
UINT16
RO
0x0000 (0
dec
)
App0:12
Data-Exchange Re-
peat Counter (B-
Slave)
This counter is incremented if the data exchange has to
be repeated (slave responded incorrectly or not all)
UINT16
RO
0x0000 (0
dec
)