Configuration
CU8130-0240
38
Version: 1.1
7.5
TwinCAT interface
7.5.1
FB_GetUPSStatus
Requirements:
• Beckhoff UPS software components have been installed:
◦ Windows 7, Windows Embedded Standard 7 and higher: Configuration dialog under "
Start-
>Programs->Beckhoff->UPS Software Components"
.
◦ NT4, Win2K, WinXP, WinXP embedded: Additional tabs under "
Control Panel->Power Options-
>Beckhoff UPS Configuration"
or "
Control Panel->Power Options->UPS
".
◦ Beckhoff CE devices with 24V UPS support are delivered with a special Beckhoff Battery Driver for
Windows CE. In these devices the driver is included in the standard CE image.
• The UPS has been activated and configured. You can find more information about UPS configuration
in the corresponding advanced UPS software and device documentation.
◦ Windows 7, Windows Embedded Standard 7 and higher: Configuration dialog under "
Start-
>Programs->Beckhoff->UPS Software Components"
.
◦ NT4, Win2K, WinXP, WinXP embedded: Configuration dialog under "
Control Panel->Power
Options->Beckhoff UPS Configuration"
.
◦ Windows CE: By default the UPS function is disabled and must be enabled via a RegFile. Newer
images have a configuration dialog under "
Start->Control Panel->BECKHOFF UPS Configuration"
.
The function block FB_GetUPSStatus reads the status of the UPS hardware from the PLC. The function
block is level triggered, which means that the status information of the UPS is only cyclically read while the
bEnable
input is set. To maintain system loading at a low level, the status information is only read
approximately every 4.5 s. When the
bValid
output is set, the most recently read data is valid. The most
recent read cycle was, in other words, executed without error. If an error occurs, the read cycle is repeated,
and the error signal is automatically reset as soon as the cause of the error (e.g. no communication with the
UPS) has been corrected.
VAR_INPUT
VAR_INPUT
sNetId : T_AmsNetId;
nPort : T_AmsPort;(* 0 = Windows UPS service / Windows Battery Driver *)
bEnable : BOOL;
END_VAR
sNetId
: A string with the network address of the TwinCAT computer whose UPS status is to be read can be
entered here (type: T_AmsNetID). If it is to be run on the local computer, an empty string can be entered.
nPort
: The ADS port number (type: T_AmsPort). Set this value to zero. Other port numbers are reserved for
future applications.
bEnable
: The UPS status is read cyclically if this input is set.
VAR_OUTPUT
VAR_OUTPUT
bValid :BOOL;
bError :BOOL;
nErrId :UDINT;
stStatus :ST_UPSStatus;
END_VAR
bValid
: If this output is set, the data in the ST_UPSstatus structure are valid (no error occurred during the
last reading cycle).