Configuration
CU8130-0240
42
Version: 1.1
Status in-
formation
Beckhoff BAPI
v1
Beckhoff
P24Vxxxx UPS
Beckhoff 24V
UPS on the
CP903x card
CX2100-09x4
APC
Back-
UPS
Pro
280
APC
Smart-
UPS 420
Description
pired. Imple-
mented in the
UPS software
version >=
3.0.0.8;
Under Tempera-
ture
(bit 11 set)
was detected and
the charging of the
battery was inter-
rupted.
Requires a newer
(second) hard-
ware revision.
Im-
plemented in the
UPS software ver-
sion >= 3.0.0.18.
Fuse Not Ok
(bit
12 set). The
"Smart Battery"
fuse is defective or
not available.
Re-
quires a newer
(second) hard-
ware revision.
Im-
plemented in the
UPS software ver-
sion >= 3.0.0.18.
Requirements
Development en-
vironment
Target platform
UPS hardware
PLC libraries to be
integrated (cate-
gory group)
TwinCAT v3.1.0
PC or CX (x86, x64, ARM)
• Beckhoff BAPI v1;
• Beckhoff P24Vxxxx;
• Beckhoff CP903x card (PCI/ISA);
• Beckhoff CX2100-09x4 models
(e.g. CX2100-0904 or
CX2100-0914 + "Smart Battery"
CX2900-0192);
• The APC devices that come
supplied with Beckhoff Industrial
PC support the Smart protocol
and can be configured with the
Windows UPS service.
Tc2_IoFunctions
(IO)