Configuration
CU8130-0240
31
Version: 1.1
7.3.1
Device configuration dialog
Dialog with device-specific settings.
Setting or
function
Value range
Default value
Description
Battery Type
(combo box)
C9900-U330,
C9900-U332,
User-Defined
C9900-U330
Configures the used Beckhoff battery pack type.
Battery Type
(edit field)
0..99
1
Available only if "User-Defined" battery type is selected.
The setting is necessary, for instance, to be able to
calculate the remaining charge available under battery
operation.
Nominal
Battery
Capacity
0..99900 [mAh]
3400
Available only if "User-Defined" battery type is
selected.The setting is necessary, for instance, to be able
to calculate the remaining charge available under battery
operation.
Internal
Battery
Resistance
0..999 [mOhm]
120
Available only if "User-Defined" battery type is
selected.The setting is necessary, for instance, to be able
to calculate the remaining charge available under battery
operation.
Battery
replace
service
interval
0..480 [months]
60 (5 years)
and checkbox
not enabled
The user is able to enter/configure the battery replace
service interval (number of months) before first warning is
logged to Windows eventlog.
Use the checkbox to activate or deactivate the
functionality. The functionality is only available if the
battery change date and system time (in the task bar) is
also set/configured.
The UPS service compares the configured battery
change date to the configured service interval at service
start. If battery replace date + service interval >= current
system date => Windows Eventlog warning message will
be logged.
The warning message do not reflects the real battery
condition and can be used as reminder to check the real
battery condition or battery age.