Commissioning
CU8130-0240
18
Version: 1.1
6.1.1
Fastening to the DIN rail
For optimal dissipation of heat, mount the UPS horizontally in the control cabinet on a DIN rail. The housing
is designed so that the UPS can be held against the DIN rail and snapped onto it.
Requirements:
• DIN rail of the type TS35x15 2.3 according to EN 60715.
Fasten the UPS to the DIN rail as follows:
1. First, place the UPS against the lower edge of the DIN rail.
2. Tilt the upper part of the UPS towards the DIN rail.
3. Lightly press the UPS against the DIN rail and upwards.
ð
As soon as you press the UPS upwards, the lower springs of the DIN rail adapters give way. In this
manner, the UPS can be attached on the upper edge of the DIN rail.
4. Attach the UPS to the upper edge of the DIN rail.
ð
You have successfully mounted the UPS. Check again that the mounting is correct and that the UPS is
engaged on the DIN rail.
Содержание CU8130-0240
Страница 1: ...Manual EN CU8130 0240 Uninterruptible Power Supply Battery backed 11 26 2021 Version 1 1 ...
Страница 2: ......
Страница 56: ......