Use of the STO function
AX8911
30
Version: 1.2.0
Fig. 12: TwinSAFE outputs connected to STO inputs
Using the STO inputs with a third-party safety controller
It must also be ensured that test pulses are generated when using a third-party safety controller or safe
output. The user must ensure that the test pulse length and frequency do not lead to a switch-off of the STO
channels or the AX8911. A filter with a filter time of 3.5 ms is implemented within the logic of the AX8911.
NOTE
Safety assessment
When using a third-party safety controller, the safety assessment must be carried out by the user or the
machine manufacturer.
Fig. 13: Safe outputs from a third-party manufacturer connected to STO inputs
If the safety controller is unable to implement test pulses at the outputs, but instead supplies only static
24 V
DC
signals, the user must implement the wiring in such a way that a fault exclusion is permitted for the
wiring. Further information about fault exclusions can be found in EN ISO 13849-2.