Product description
AX8911
18
Version: 1.2.0
The AX8911 TwinSAFE Drive Option card can be used for safety-related applications within the meaning of
IEC 61508:2010 up to SIL 3, EN 62061:2005/A1:2013/A2:2015 up to SILCL3 and EN ISO 13849-1:2015 up
to PL e (Cat.4).
In terms of safety-related parameters, the Safety-over-EtherCAT communication is already considered with
1% of SIL3 according to the protocol specification.
Calculation examples for the total PFH
D
or total MTTF
D
values can be found in the TwinSAFE Application
Guide.
4.5
AX8911 project design limits
Project design limits
The maximum project design size of the AX8911 is limited by the available memory. This is man-
aged dynamically. The values specified in the following table are therefore only guide values and
may differ from the actual values, depending on the safety project.
TwinSAFE connections
max. 8
(up to 12 CRCs in total; 1 CRC is required for a TwinSAFE connection
with 1 or 2 byte safe data.)
Safe data per TwinSAFE
connection
maximum 24 byte (telegram length 51 byte)
TwinSAFE blocks
maximum 512 (ESTOP with complete input and output mapping)
TwinSAFE groups
max. 128
TwinSAFE user
40 max.
Standard PLC inputs
dynamic (memory-dependent), max. 54 byte
Standard PLC outputs
dynamic (memory-dependent), max. 62 byte