SPECIFICATIONS/FEATURES FOR
ALARM BOARDS

MC4000-A w/Optional Base Alarm Board
(Inputs/Outputs)

NOTE: If this alarm board was not originally factory
installed, it can be field-installed at anytime.  Bard
part number is AB3000-A.

MC4000-B w/Enhanced Version Alarm Board
(Additional Outputs) plus MC4000-A Inputs/Outputs

NOTE: If this alarm board was not originally factory
installed, it can be field-installed at anytime.  Bard
part number is AB3000-B.

Note:

 All alarm and output relays are dry contacts rated

1A @ 24 VAC.

BASIC MC4000 CONTROLLER
INPUT/OUTPUT SPECIFICATIONS

MC4000 CONTROLLER CONNECTIONS

Located on Main Controller Board

Unit #1

C – 24VAC common
R – 24VAC hot
G – fan (Form A, NO)
Y1 – 1

st

-stage cool (Form A, NO)

Y2 – 2

nd

-stage cool (Form A, NO)

W – heat (Form A, NO)

Unit #2

C – 24VAC common
R – 24VAC hot
G – fan (Form A, NO)
Y1 – 1

st

-stage cool (Form A, NO)

Y2 – 2

nd

-stage cool (Form A, NO)

W – heat (Form A, NO)

F1-F2

Fire/smoke interface
Shipped with jumper installed (a)

48Vdc

Back-up power input
-24Vdc or –48Vdc
-20V to –56V range

Local

Main sensor, 12-inch leads
CU – copper, AG – silver
Polarity sensitive

Rem 1

Optional remote indoor sensor
CU – copper, AG – silver
Polarity sensitive

Rem 2

Optional remote indoor sensor
CU – copper, AG – silver
Polarity sensitive

Gen

Generator interface G1-G2
Shipped with jumper installed (a)

H1-H2

Humidity controller input
Requires optional controller
Field installed

(a) These connections require either jumper or Normally

Closed (NC) relay contact at the Fire/Smoke and Generator
interface for Controller to function.

Inputs

Lockout 1

2,3 – input from HVAC #1

Lockout 2

2, 3 – input from HVAC #2

Outputs

Smoke/Fire

Form C (SPDT)

Lockout 1

Form C (SPDT)
Refrigerant alarm HVAC #1

Lockout 2

Form C (SPDT)
Refrigerant alarm HVAC #2

Power Loss 1

Form C (SPDT)
Power loss HVAC #1

Power Loss 2

Form C (SPDT)
Power loss HVAC #2

Low Temp

Form C (SPDT)
Low temperature alarm

High Temp 1

Form C (SPDT)
High temperature alarm #1

High Temp 2

Form C (SPDT)
High temperature alarm #2

Controller

Form C (SPDT)
Controller failure alarm

Econ 1

E, F - Form A (NO)
See note (b)

Econ 2

E, F - Form A (NO)
See note (b)

2

nd

 Stage (c)

Form C (SPDT)
2

nd

-stage cooling alarm

(b) Make these connections to terminals E & F in HVAC 1

and 2 respectively if desired to have economizers open for
emergency ventilation at High Temp Alarm #2 setpoint
condition.

(c) For units with 2-stage compressors, 2nd stage cooling

alarm activates on cooling Stage 3 initiation.

Alarm relays can be wired for NO (close on alarm) or NC (open on alarm) strategy.  Alarm relays can be used individually if
there are enough available building alarm points, or can be arranged into smaller groups or even a single group so that all
alarm capabilities can be utilized.  When multiple alarms are grouped together and issued as a single alarm there will be no
off-site indication of which specific problem may have occurred, only that one of the alarms in the group has been triggered.
The individual alarm problem will be displayed on the LED display on face of the controller.

NOTE:

Sensors are

solid state,

not RTD.

Use Bard

sensors only.

Note:

 All alarm relay outputs have 10-second delay

before issuing to protect against nuisance alarm signals.

Содержание MC4000 SERIES

Страница 1: ...STATE DUAL UNIT LEAD LAG CONTROLLER INSTALLATION INSTRUCTIONS REPLACEMENT PARTS LIST Manual No 2100 563C Supersedes 2100 563B File Vol III Tab 19 Date 06 25 12 Bard Manufacturing Company Inc Bryan Oh...

Страница 2: ...Strategy 33 MC4000 Label 35 Figure 17 Parts List Description Diagram 36 Tables Table 1 Hook Up Diagram Selection 17 Table Parts List 37 Getting Other Information and Publications 3 MC4000 General Info...

Страница 3: ...90B and Air Conditioning Systems FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washington DC 20009 Telephone 202 483 9370 Fax...

Страница 4: ...ired for special applications or user preference The MC4000 can be equipped with one of two alarm boards and these can be factory installed or installed at any time in the field if so desired Should t...

Страница 5: ...The standard local temperature sensor has 12 leads and comes installed from the factory A secondary sensor is located internally on the main controller board and serves as a reference and back up sen...

Страница 6: ...Smoke and Generator interface for Controller to function Inputs Lockout 1 2 3 input from HVAC 1 Lockout 2 2 3 input from HVAC 2 Outputs Smoke Fire Form C SPDT Lockout 1 Form C SPDT Refrigerant alarm...

Страница 7: ...ol located in the electrical control panel of the air conditioners being controlled by the lead lag controller To eliminate the 60 second blower off delay disconnect and isolate the wire that is facto...

Страница 8: ...u t a r e p m e T n A F c n o i t a r e p o r e w o l b s u o u n i t n o C h t o B d a e L e n o N e n o N g e d C r o F n i s e t a r e p o m e t s y s r e l l o r t n o C C r o F F t l A e c n e u...

Страница 9: ...conomizer 1st stage cooling set point is the setting SP input into the controller Factory default is 77F 25C On a call for cooling the blower of the lead unit will come on immediately if not already o...

Страница 10: ...default setting user selectable 2 6F warmer than Stage 1 On a call for 2nd Stage cooling the blower of the lag unit is turned on if not already on See Blower Operation and the Stage 2 LED will blink f...

Страница 11: ...operation COOLING OPERATING SEQUENCES FOR NON ALTERNATING LEAD LEAD LAG LAG CONFIGURATION Note Heat pumps cannot be operated in Non Alternating Lead Lead Lag Lag sequence Selecting Heat Pump Yes will...

Страница 12: ...mizer control If outdoor conditions are not acceptable for free cooling the compressor will automatically operate instead of the economizer 4th cooling set point is 2F default setting user selectable...

Страница 13: ...to operate and the compressor will operate on compressor Stage 2 full capacity If the compressor is already operating on Stage 1 partial capacity because outside free cooling range the compressor wil...

Страница 14: ...age should appear For Vista or Windows 7 1 Open Control Panel click Network Internet 2 Click Network Sharing Center 3 Click Local Area Network link 4 Click Properties 5 Highlight Internet Protocol Ver...

Страница 15: ...Alarm b Low Temp Clear or Alarm c High Temp 1 Clear or Alarm d High Temp 2 Clear or Alarm e Controller Failure Clear or Alarm SETPOINTS PAGE Note Read level authority can view this screen but cannot...

Страница 16: ...buttons while the controller is in the normal operating run mode 2 Press and hold the Advance Change Save button and the Up and Down arrow buttons simultaneously for 20 seconds until the display show...

Страница 17: ...o C d r a o B r e w e N T M W N O C E o N r e z i m o n o c E n o i t a c i n u m m o C d r a o B r e w e N T M W N O C E r e z i m o n o c E 0 0 0 4 B C h t i w n o i t a c i n u m m o C d r a o B e...

Страница 18: ...Manual 2100 563C Page 18 of 40 FIGURE 2 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS NO ECONOMIZERS...

Страница 19: ...Manual 2100 563C Page 19 of 40 FIGURE 3 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS NO ECONOMIZER WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 20: ...Manual 2100 563C Page 20 of 40 FIGURE 4 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS NO ECONOMIZERS WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 21: ...Manual 2100 563C Page 21 of 40 FIGURE 5 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS...

Страница 22: ...Manual 2100 563C Page 22 of 40 FIGURE 6 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS...

Страница 23: ...Manual 2100 563C Page 23 of 40 FIGURE 7 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 24: ...Manual 2100 563C Page 24 of 40 FIGURE 8 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 25: ...Manual 2100 563C Page 25 of 40 FIGURE 9 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS...

Страница 26: ...Manual 2100 563C Page 26 of 40 FIGURE 10 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS...

Страница 27: ...Manual 2100 563C Page 27 of 40 FIGURE 11 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 28: ...Manual 2100 563C Page 28 of 40 FIGURE 12 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 29: ...Manual 2100 563C Page 29 of 40 FIGURE 13 CONTROLLERCONNECTIONS HEAT PUMPS NO ECONOMIZER...

Страница 30: ...Manual 2100 563C Page 30 of 40 FIGURE 14 CONTROLLERCONNECTIONS HEAT PUMPS NO ECONOMIZER WITH OPTIONAL ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 31: ...hod to issue an alarm signal that the lead air conditioner is down or not delivering full capacity and that the lag air conditioner is now operating REFRIGERANT PRESSURE ALARMS Air conditioners with J...

Страница 32: ...loose to protect it from possible damage during installation of the wiring to main controller board and or the alarm board It is polarity sensitive and is keyed so it can only be installed in correct...

Страница 33: ...loose to protect it from possible damage during installation of the wiring to main controller board and or the alarm board It is polarity sensitive and is keyed so it can only be installed in correct...

Страница 34: ...wn If no buttons are pushed within thirty 30 seconds the controller will automatically revert back to RUN mode To reset all controller settings to the factory default values press the PROGRAM button f...

Страница 35: ...or 18 3 to 32 2C Default is 77F 25C 5 Deadband between cooling and heating setpoint 2 to 40F or 1 1 to 22 2C Default is 17F 9 4C 6 Continuous blower operation None Lead Both Default is None 7 Degree...

Страница 36: ...Manual 2100 563C Page 36 of 40 FIGURE 17 PARTS LIST DESCRIPTION DIAGRAM MIS 2954 12 9 3 4 5 7 6 11 2 1 10 8...

Страница 37: ...o B m r a l A X X X 3 1 2 0 2 1 6 8 B d r a o B m r a l A X X X 4 2 2 0 2 1 6 8 y a l p s i D m r a l A X X X X X X 5 4 0 3 4 3 1 1 t e k c a r B t r o p p u S X X X X X 6 4 5 8 3 2 5 1 r o o D x o B...

Страница 38: ...Manual 2100 563C Page 38 of 40 This page intentionally left blank...

Страница 39: ...Manual 2100 563C Page 39 of 40 This page intentionally left blank...

Страница 40: ...Manual 2100 563C Page 40 of 40 This page intentionally left blank...

Отзывы: