USER PAGE

1.

The designated Admin person can assign up to 9
additional users and set-up as Admin, Write or
Read authority.

2.

User Name and password must be assigned, each
must be at least 3 characters long, and are case
sensitive.

3.

Only “Admin” can add, change or delete users and
has access to all controller pages.

4.

“Write” can make changes to the controller
settings and operating characteristics, and has
access to only Log In, System Status, Setpoints,
and Log Out pages.

5.

“Read” can only view Status and Setpoints pages
and cannot make any changes.

SYSTEM STATUS PAGE

1.

This page shows the overall HVAC status of:
a. Active cooling or heating stages or

dehumidification mode (requires humidity
sensor)

b. Active controller outputs (blower, cooling

Stage 1 or 2, heating) to each air conditioner

c. Which unit is the Lead unit
d. Power loss or refrigerant lock-out for each air

conditioner

e. If economizers are used if on or off (Note:

older style EIFM economizers require a simple
relay kit for this feature to work, Bard Part
Number 8620-221)

2.

General status of:
a. Dehumidification Active or not
b. Backup Generator Active or not (if tied to

generator run controls to inhibit lag unit
operation during generator run)

c. Alarm board connected or not
d. Controller system Locked or Unlocked
e. Comfort mode Active or not

3.

Temperatures:
a. Average temperature (if more than ones sensor

used, if not will read same as Local sensor)

b. Local sensor at controller
c. Remote 1 or Remote 2 if connected

4.

General Alarm Status:
a. Fire/Smoke, Clear or Alarm
b. Low Temp, Clear or Alarm
c. High Temp #1, Clear or Alarm
d. High Temp #2, Clear or Alarm
e. Controller Failure, Clear or Alarm

SETPOINTS PAGE (Note: “Read” level authority
can view this screen but cannot make any changes.
“Admin” and “Write” authority can make changes)

1.

General Setpoints
a. On initial installation and start-up all selectable

characteristics are set to factory default
settings.

b. Each of these points has a drop-down menu for

ease of use.

2.

Alarm Board Setpoints
a. Low temperature alarm setpoint
b. High temperature alarm #1 setpoint
c. High temperature alarm #2 setpoint

3.

System Overrides
a. System 1 Cooling Override
b. System 1 Heating Override
c. System 2 Cooling Override
d. System 2 Heating Override
e. Turn Power On to the System (Note: Cannot

remotely turn the controller system Off)

f. Lock/Unlock Controller
g. Advance Lead to Lag Unit
h. Comfort Mode
i. Restore System Defaults
j. Reset Controller. There are built-in routines to

prevent the controller system from getting
“locked up”, but this also allows a manual
remote reset as a backup before having a
service call to the site.

LOG OUT BUTTON

1.

Clicking this button will automatically log you off
the controller remote access.

2.

To log back in will require entering assigned IP
address into your browser and entering valid User
Name and Password.

CONNECT TO NETWORK

1.

After initial set-up using laptop computer,
disconnect computer cable from the Ethernet port
and connect the CAT 5 or CAT 6 network cable.

2.

Remote access is now available using the assigned
IP address and valid User Name and Password
(case sensitive).

CB4000 COMMUNICATION BOARD

RESET BUTTON TO RETURN TO DEFAULT CONTROLLER SETTINGS

ETHERNET PORT

IP DEFAULT ADDRESS RESET

PHONE JACK
CONNECTION
TO MAIN
CONTROLLER
BOARD

Содержание MC4000 SERIES

Страница 1: ...STATE DUAL UNIT LEAD LAG CONTROLLER INSTALLATION INSTRUCTIONS REPLACEMENT PARTS LIST Manual No 2100 563C Supersedes 2100 563B File Vol III Tab 19 Date 06 25 12 Bard Manufacturing Company Inc Bryan Oh...

Страница 2: ...Strategy 33 MC4000 Label 35 Figure 17 Parts List Description Diagram 36 Tables Table 1 Hook Up Diagram Selection 17 Table Parts List 37 Getting Other Information and Publications 3 MC4000 General Info...

Страница 3: ...90B and Air Conditioning Systems FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washington DC 20009 Telephone 202 483 9370 Fax...

Страница 4: ...ired for special applications or user preference The MC4000 can be equipped with one of two alarm boards and these can be factory installed or installed at any time in the field if so desired Should t...

Страница 5: ...The standard local temperature sensor has 12 leads and comes installed from the factory A secondary sensor is located internally on the main controller board and serves as a reference and back up sen...

Страница 6: ...Smoke and Generator interface for Controller to function Inputs Lockout 1 2 3 input from HVAC 1 Lockout 2 2 3 input from HVAC 2 Outputs Smoke Fire Form C SPDT Lockout 1 Form C SPDT Refrigerant alarm...

Страница 7: ...ol located in the electrical control panel of the air conditioners being controlled by the lead lag controller To eliminate the 60 second blower off delay disconnect and isolate the wire that is facto...

Страница 8: ...u t a r e p m e T n A F c n o i t a r e p o r e w o l b s u o u n i t n o C h t o B d a e L e n o N e n o N g e d C r o F n i s e t a r e p o m e t s y s r e l l o r t n o C C r o F F t l A e c n e u...

Страница 9: ...conomizer 1st stage cooling set point is the setting SP input into the controller Factory default is 77F 25C On a call for cooling the blower of the lead unit will come on immediately if not already o...

Страница 10: ...default setting user selectable 2 6F warmer than Stage 1 On a call for 2nd Stage cooling the blower of the lag unit is turned on if not already on See Blower Operation and the Stage 2 LED will blink f...

Страница 11: ...operation COOLING OPERATING SEQUENCES FOR NON ALTERNATING LEAD LEAD LAG LAG CONFIGURATION Note Heat pumps cannot be operated in Non Alternating Lead Lead Lag Lag sequence Selecting Heat Pump Yes will...

Страница 12: ...mizer control If outdoor conditions are not acceptable for free cooling the compressor will automatically operate instead of the economizer 4th cooling set point is 2F default setting user selectable...

Страница 13: ...to operate and the compressor will operate on compressor Stage 2 full capacity If the compressor is already operating on Stage 1 partial capacity because outside free cooling range the compressor wil...

Страница 14: ...age should appear For Vista or Windows 7 1 Open Control Panel click Network Internet 2 Click Network Sharing Center 3 Click Local Area Network link 4 Click Properties 5 Highlight Internet Protocol Ver...

Страница 15: ...Alarm b Low Temp Clear or Alarm c High Temp 1 Clear or Alarm d High Temp 2 Clear or Alarm e Controller Failure Clear or Alarm SETPOINTS PAGE Note Read level authority can view this screen but cannot...

Страница 16: ...buttons while the controller is in the normal operating run mode 2 Press and hold the Advance Change Save button and the Up and Down arrow buttons simultaneously for 20 seconds until the display show...

Страница 17: ...o C d r a o B r e w e N T M W N O C E o N r e z i m o n o c E n o i t a c i n u m m o C d r a o B r e w e N T M W N O C E r e z i m o n o c E 0 0 0 4 B C h t i w n o i t a c i n u m m o C d r a o B e...

Страница 18: ...Manual 2100 563C Page 18 of 40 FIGURE 2 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS NO ECONOMIZERS...

Страница 19: ...Manual 2100 563C Page 19 of 40 FIGURE 3 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS NO ECONOMIZER WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 20: ...Manual 2100 563C Page 20 of 40 FIGURE 4 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS NO ECONOMIZERS WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 21: ...Manual 2100 563C Page 21 of 40 FIGURE 5 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS...

Страница 22: ...Manual 2100 563C Page 22 of 40 FIGURE 6 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS...

Страница 23: ...Manual 2100 563C Page 23 of 40 FIGURE 7 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 24: ...Manual 2100 563C Page 24 of 40 FIGURE 8 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 25: ...Manual 2100 563C Page 25 of 40 FIGURE 9 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS...

Страница 26: ...Manual 2100 563C Page 26 of 40 FIGURE 10 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS...

Страница 27: ...Manual 2100 563C Page 27 of 40 FIGURE 11 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 28: ...Manual 2100 563C Page 28 of 40 FIGURE 12 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 29: ...Manual 2100 563C Page 29 of 40 FIGURE 13 CONTROLLERCONNECTIONS HEAT PUMPS NO ECONOMIZER...

Страница 30: ...Manual 2100 563C Page 30 of 40 FIGURE 14 CONTROLLERCONNECTIONS HEAT PUMPS NO ECONOMIZER WITH OPTIONAL ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 31: ...hod to issue an alarm signal that the lead air conditioner is down or not delivering full capacity and that the lag air conditioner is now operating REFRIGERANT PRESSURE ALARMS Air conditioners with J...

Страница 32: ...loose to protect it from possible damage during installation of the wiring to main controller board and or the alarm board It is polarity sensitive and is keyed so it can only be installed in correct...

Страница 33: ...loose to protect it from possible damage during installation of the wiring to main controller board and or the alarm board It is polarity sensitive and is keyed so it can only be installed in correct...

Страница 34: ...wn If no buttons are pushed within thirty 30 seconds the controller will automatically revert back to RUN mode To reset all controller settings to the factory default values press the PROGRAM button f...

Страница 35: ...or 18 3 to 32 2C Default is 77F 25C 5 Deadband between cooling and heating setpoint 2 to 40F or 1 1 to 22 2C Default is 17F 9 4C 6 Continuous blower operation None Lead Both Default is None 7 Degree...

Страница 36: ...Manual 2100 563C Page 36 of 40 FIGURE 17 PARTS LIST DESCRIPTION DIAGRAM MIS 2954 12 9 3 4 5 7 6 11 2 1 10 8...

Страница 37: ...o B m r a l A X X X 3 1 2 0 2 1 6 8 B d r a o B m r a l A X X X 4 2 2 0 2 1 6 8 y a l p s i D m r a l A X X X X X X 5 4 0 3 4 3 1 1 t e k c a r B t r o p p u S X X X X X 6 4 5 8 3 2 5 1 r o o D x o B...

Страница 38: ...Manual 2100 563C Page 38 of 40 This page intentionally left blank...

Страница 39: ...Manual 2100 563C Page 39 of 40 This page intentionally left blank...

Страница 40: ...Manual 2100 563C Page 40 of 40 This page intentionally left blank...

Отзывы: