manualshive.com logo in svg
background image

Manual

2100-563C

Page

9 of 40

HUMIDITY CONTROL OPTION

Note:

 

This function is not available if controller is

configured for heat pump.

The standard air conditioning system can be adapted to
perform dehumidification control by addition of a
simple humidity controller that closes-on-rise, and is
connected to terminals H1 and H2 on the main controller
board.  Recommended Bard Part #8403-038 (H600A
1014).  Both HVAC units must be equipped with electric
heat for this sequence to work properly.  See appropriate
connection diagram - Figures 1 - 12 for this connection:

1. Temperature control always has priority over

dehumidification.  If there is any stage of cooling
demand active, the dehumidification sequence is
locked out.

2. If all stages of cooling are satisfied, and relative

humidity is above the set point of humidity
controller:

a. The green “Dehumid. Operation” light will come

on, and the lag unit compressor and blower will
operate until the set point of humidity controller
is satisfied (or cancelled by a call for cooling).

b. If the space temperature drops to 67F, the electric

heater of the lead unit will cycle to help maintain
building temperature.  It will cycle off at 69F.

c. If space temperature drops to 64F, the Stage 2

Heating light will come on and the lag unit
compressor operating for dehumidification mode
will cycle off until the building temperature rises
above 65F from 1st stage heat and building load.
The green “Dehumid. Operation” light stays on
during this sequence, and when Stage 2 Heating
light is Off, the compressor is On.  The electric
heater in lag unit is locked out in
dehumidification mode.

Lag unit outputs G, Y1 and Y2 are all switched on
during dehumidification sequence.  This is true for both
alternating and non-alternating controller configurations.

COOLING OPERATING SEQUENCES FOR
ALTERNATING LEAD/LAG/LEAD/LAG
CONFIGURATION

1.

1-Stage Compressor Units No Economizer

1

st

 stage cooling set point is the setting (SP) input into

the controller. Factory default is 77F (25C). On a call for
cooling the blower of the lead unit will come on
immediately (if not already on – See Blower Operation),
and the Stage 1 LED will blink for 10-seconds before
going solid, at which time the compressor will start.

2

nd

 cooling set point is 4F (default setting, user

selectable 2-6F) warmer than Stage 1. On a call for 2

nd

Stage cooling the blower of the lag unit is turned on (if
not already on – See Blower Operation), and the Stage 2
LED will blink for 10-seconds before going solid, at
which time the compressor will start.

3

rd

 and 4

th

 stages are functional outputs but there is

nothing to be controlled.

2.

2-Stage Compressor Units No Economizer

1

st

 stage cooling set point is the setting (SP) input into the

controller. Factory default is 77F (25C). On a call for
cooling the blower of the lead unit will come on
immediately (if not already on – See Blower Operation),
and the Stage 1 LED will blink for 10-seconds before
going solid, at which time the lead unit compressor will
start in compressor Stage 1 partial capacity operation.

2

nd

 cooling set point is 4F (default setting, user selectable

2-6F) warmer than Stage 1. On a call for 2

nd

 Stage

cooling the blower of the lag unit is turned on (if not
already on – See Blower Operation), and the Stage 2
LED will blink for 10-seconds before going solid, at
which time the lag unit compressor will start in
compressor Stage 1 partial capacity operation.

3

rd

 cooling set point is 2F (default setting, user selectable

2-3F) warmer than Stage 2. On a call for 3

rd

 Stage

cooling the Stage 3 LED comes on solid (no delay), and
the lead unit compressor will switch to compressor Stage
2 full capacity operation.

Humidity controller set point should be in 50-60%
relative humidity area:  Setting controller to lower
settings will result in excessive operating time and
operating costs for the electric reheat, and in
extreme cases could cause evaporator (indoor) coil
freeze-up if there are periods of light internal
equipment (heat) loading.

CAUTION

Содержание MC4000 SERIES

Страница 1: ...STATE DUAL UNIT LEAD LAG CONTROLLER INSTALLATION INSTRUCTIONS REPLACEMENT PARTS LIST Manual No 2100 563C Supersedes 2100 563B File Vol III Tab 19 Date 06 25 12 Bard Manufacturing Company Inc Bryan Oh...

Страница 2: ...Strategy 33 MC4000 Label 35 Figure 17 Parts List Description Diagram 36 Tables Table 1 Hook Up Diagram Selection 17 Table Parts List 37 Getting Other Information and Publications 3 MC4000 General Info...

Страница 3: ...90B and Air Conditioning Systems FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washington DC 20009 Telephone 202 483 9370 Fax...

Страница 4: ...ired for special applications or user preference The MC4000 can be equipped with one of two alarm boards and these can be factory installed or installed at any time in the field if so desired Should t...

Страница 5: ...The standard local temperature sensor has 12 leads and comes installed from the factory A secondary sensor is located internally on the main controller board and serves as a reference and back up sen...

Страница 6: ...Smoke and Generator interface for Controller to function Inputs Lockout 1 2 3 input from HVAC 1 Lockout 2 2 3 input from HVAC 2 Outputs Smoke Fire Form C SPDT Lockout 1 Form C SPDT Refrigerant alarm...

Страница 7: ...ol located in the electrical control panel of the air conditioners being controlled by the lead lag controller To eliminate the 60 second blower off delay disconnect and isolate the wire that is facto...

Страница 8: ...u t a r e p m e T n A F c n o i t a r e p o r e w o l b s u o u n i t n o C h t o B d a e L e n o N e n o N g e d C r o F n i s e t a r e p o m e t s y s r e l l o r t n o C C r o F F t l A e c n e u...

Страница 9: ...conomizer 1st stage cooling set point is the setting SP input into the controller Factory default is 77F 25C On a call for cooling the blower of the lead unit will come on immediately if not already o...

Страница 10: ...default setting user selectable 2 6F warmer than Stage 1 On a call for 2nd Stage cooling the blower of the lag unit is turned on if not already on See Blower Operation and the Stage 2 LED will blink f...

Страница 11: ...operation COOLING OPERATING SEQUENCES FOR NON ALTERNATING LEAD LEAD LAG LAG CONFIGURATION Note Heat pumps cannot be operated in Non Alternating Lead Lead Lag Lag sequence Selecting Heat Pump Yes will...

Страница 12: ...mizer control If outdoor conditions are not acceptable for free cooling the compressor will automatically operate instead of the economizer 4th cooling set point is 2F default setting user selectable...

Страница 13: ...to operate and the compressor will operate on compressor Stage 2 full capacity If the compressor is already operating on Stage 1 partial capacity because outside free cooling range the compressor wil...

Страница 14: ...age should appear For Vista or Windows 7 1 Open Control Panel click Network Internet 2 Click Network Sharing Center 3 Click Local Area Network link 4 Click Properties 5 Highlight Internet Protocol Ver...

Страница 15: ...Alarm b Low Temp Clear or Alarm c High Temp 1 Clear or Alarm d High Temp 2 Clear or Alarm e Controller Failure Clear or Alarm SETPOINTS PAGE Note Read level authority can view this screen but cannot...

Страница 16: ...buttons while the controller is in the normal operating run mode 2 Press and hold the Advance Change Save button and the Up and Down arrow buttons simultaneously for 20 seconds until the display show...

Страница 17: ...o C d r a o B r e w e N T M W N O C E o N r e z i m o n o c E n o i t a c i n u m m o C d r a o B r e w e N T M W N O C E r e z i m o n o c E 0 0 0 4 B C h t i w n o i t a c i n u m m o C d r a o B e...

Страница 18: ...Manual 2100 563C Page 18 of 40 FIGURE 2 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS NO ECONOMIZERS...

Страница 19: ...Manual 2100 563C Page 19 of 40 FIGURE 3 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS NO ECONOMIZER WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 20: ...Manual 2100 563C Page 20 of 40 FIGURE 4 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS NO ECONOMIZERS WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 21: ...Manual 2100 563C Page 21 of 40 FIGURE 5 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS...

Страница 22: ...Manual 2100 563C Page 22 of 40 FIGURE 6 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS...

Страница 23: ...Manual 2100 563C Page 23 of 40 FIGURE 7 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 24: ...Manual 2100 563C Page 24 of 40 FIGURE 8 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 25: ...Manual 2100 563C Page 25 of 40 FIGURE 9 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS...

Страница 26: ...Manual 2100 563C Page 26 of 40 FIGURE 10 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS...

Страница 27: ...Manual 2100 563C Page 27 of 40 FIGURE 11 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 28: ...Manual 2100 563C Page 28 of 40 FIGURE 12 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 29: ...Manual 2100 563C Page 29 of 40 FIGURE 13 CONTROLLERCONNECTIONS HEAT PUMPS NO ECONOMIZER...

Страница 30: ...Manual 2100 563C Page 30 of 40 FIGURE 14 CONTROLLERCONNECTIONS HEAT PUMPS NO ECONOMIZER WITH OPTIONAL ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 31: ...hod to issue an alarm signal that the lead air conditioner is down or not delivering full capacity and that the lag air conditioner is now operating REFRIGERANT PRESSURE ALARMS Air conditioners with J...

Страница 32: ...loose to protect it from possible damage during installation of the wiring to main controller board and or the alarm board It is polarity sensitive and is keyed so it can only be installed in correct...

Страница 33: ...loose to protect it from possible damage during installation of the wiring to main controller board and or the alarm board It is polarity sensitive and is keyed so it can only be installed in correct...

Страница 34: ...wn If no buttons are pushed within thirty 30 seconds the controller will automatically revert back to RUN mode To reset all controller settings to the factory default values press the PROGRAM button f...

Страница 35: ...or 18 3 to 32 2C Default is 77F 25C 5 Deadband between cooling and heating setpoint 2 to 40F or 1 1 to 22 2C Default is 17F 9 4C 6 Continuous blower operation None Lead Both Default is None 7 Degree...

Страница 36: ...Manual 2100 563C Page 36 of 40 FIGURE 17 PARTS LIST DESCRIPTION DIAGRAM MIS 2954 12 9 3 4 5 7 6 11 2 1 10 8...

Страница 37: ...o B m r a l A X X X 3 1 2 0 2 1 6 8 B d r a o B m r a l A X X X 4 2 2 0 2 1 6 8 y a l p s i D m r a l A X X X X X X 5 4 0 3 4 3 1 1 t e k c a r B t r o p p u S X X X X X 6 4 5 8 3 2 5 1 r o o D x o B...

Страница 38: ...Manual 2100 563C Page 38 of 40 This page intentionally left blank...

Страница 39: ...Manual 2100 563C Page 39 of 40 This page intentionally left blank...

Страница 40: ...Manual 2100 563C Page 40 of 40 This page intentionally left blank...

Отзывы: