manualshive.com logo in svg
background image

Manual

2100-563C

Page

5 of 40

SPECIFICATIONS/FEATURES FOR BASIC
CONTROLLER

MC4000 Basic Controller

•Input power: 18-32 VAC, 60/50Hz, power is supplied from
A/C #1 and/or A/C #2
•Isolation circuitry: no line or low voltage phasing required
•Backup power: connection for -24 VDC or -48 VDC (-20 to -
56V) maintains microprocessor operation, front panel indication
& alarm relay operation during commercial power outages.
•Digital display: 4-character LCD
•Temperature display: F or C
•HVAC outputs: Form A (NO) relays (1A @ 24 VAC)
•Cooling control stages:

2 for each A/C unit (4 total) when configured for economizers
1 for each A/C unit (2 total) when configured for no economizers

•Heating Control stages:

1 for each A/C unit, 2 for each heat pump if so configured

•Dehumidification circuit: requires optional humidity
controller as input signal
•Operating temperature range: 0 to 120F (-18 to 49C)
•Storage temperature range: -20 to 140F (-29 to 60C)
•Temperature accuracy: +/- 1F from 60-85F (16-30C)

+/- 1% outside 60-85F

•Lead/lag changeover time: 0 to 30 days
•Timing accuracy: +/- 1%
•Inter-stage time delay: 10 seconds between stages
•Inter-stage differential:

Stage 1 to 2 - Range 2-6F, default is 4
Stage 2 to 3 - Range 2-3F, default is 2
Stage 3 to 4 - Range 2-3F, default is 2

•On-Off differential: 2F (1C) is standard, 4F (3C) when
“excessive cycling” mode is enabled
•Cooling set point range: 65 to 90F (18.3 to 32.2C)
•Comfort setting-Cooling 72F (22C), Heating 68F(20C), for 1 hour
•Dead band (difference between cooling and heating set
points): 2F to 40F (1.1C to 22.2C)
•Fire/smoke interface: standard NC circuit jumper, remove
for connection to building system control, shuts down both
A/C units immediately
•Memory: EEPROM for set point and changeable
parameters (maintains settings on power loss)
•Space temperature sensors: 1 local is standard, will accept up
to 2 optional 25' remote sensors, Bard part number 8612-023.
When multiple sensors are used, temperatures are averaged
•Controller Enclosure: 20-gauge pre-painted steel, 9.25"W x
13.50"H x 3.00"D, hinged cover, thirteen (13) .875" diameter
electrical knockouts
•LEDs for basic controller: Lead unit, Cooling stages 1
through 4, Heating Stages 1 – 4, Dehumidification operation
•Six (6) Push-button controls: On/Off switch-Change lead
unit-Increase & Decrease set points-Program/Save-Comfort.

MOUNTING THE CONTROLLER

Included in the controller carton is the controller and
installation instructions.
The controller should be installed on a vertical wall
approximately four (4) feet above the floor-away from drafts &
outside doors or windows.  Four (4) mounting holes are provided
for mounting to the wall and 7/8" holes for conduit connections
are provided in both the base, sides &  top of the controller.

TEMPERATURE SENSORS

The standard (local) temperature sensor has 12" leads and
comes installed from the factory.

A secondary sensor is located internally on the main
controller board and serves as a reference and back-up
sensor to the local sensor.  Any differential of +/- 12F
between the on-board and local sensor will cause the
controller to use the local sensor as its point of reference.
If the differential is greater than 12F then the controller
will check to determine the on-board sensor is reading a
temperature that is between the SP (set-point) plus 12F
and the SP minus the DB (dead-band) minus 12F.  If it is
the on-board sensor will become the valid sensor reading
and the controller will ignore the local sensor reading.  If
it is not then the controller will still use the local sensor
reading.  This is to add additional level of operational
capability in the rare event the local sensor fails.  If the
controller is operating in this mode it is indicated by the
lower left decimal point flashing in the display.  

Note: for

purposes of testing when the local sensor is manually
driven higher or lower by applying warm or cool water to
the probe the on-board sensor is inhibited for the first
30-minutes following power up, or when power is cycled
off and back on.

The controller is designed to accept 1 or 2 additional
sensors and those have 25-foot leads.  The Bard part
number for the optional sensor with 25-foot leads is
8612-023.  These can be installed as required in the
structure to address hot spots, barriers to airflow, etc.

It is recommended that the sensor lead wires be installed
in conduit for protective purposes.
If alarm boards are utilized, the highest reading of any
connected sensor will be used for high temperature alarm
and the lowest reading sensor will be used for low
temperature alarm.

TEMPERATURE SENSOR LOGIC

The standard local 

(LSEn)

 sensor monitors the

temperature at the controller location.  If this is the only
sensor connected, it will control the temperature read-out,
the space (building) temperature, and also be used for Low
and High Temperature alarm functions.
If one or more 

REMOTE

 sensors are installed and

connected (

Rem 1

 or 

Rem 2

), the temperature read-out

will display and the building will be controlled to an

average

 of all connected sensors.  If there is more than

10F difference from the highest to the lowest connected
sensor, the actual control will be governed by the hottest
sensor for cooling and the coldest sensor for heating.
If multiple temperature sensors are used, the High and
Low temperature alarms will be governed by the average
of the connected sensors.

NOTE:

 All sensors are polarity sensitive.  The copper

lead must connect to terminal CU, and the silver lead
to AG.  Sensors are solid state, not RTD.  Use only
sensors supplied by Bard.  Sensor leads can be
extended up to 200 feet.  Use 18-gauge twisted pair
with soldered connections.

Содержание MC4000 SERIES

Страница 1: ...STATE DUAL UNIT LEAD LAG CONTROLLER INSTALLATION INSTRUCTIONS REPLACEMENT PARTS LIST Manual No 2100 563C Supersedes 2100 563B File Vol III Tab 19 Date 06 25 12 Bard Manufacturing Company Inc Bryan Oh...

Страница 2: ...Strategy 33 MC4000 Label 35 Figure 17 Parts List Description Diagram 36 Tables Table 1 Hook Up Diagram Selection 17 Table Parts List 37 Getting Other Information and Publications 3 MC4000 General Info...

Страница 3: ...90B and Air Conditioning Systems FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washington DC 20009 Telephone 202 483 9370 Fax...

Страница 4: ...ired for special applications or user preference The MC4000 can be equipped with one of two alarm boards and these can be factory installed or installed at any time in the field if so desired Should t...

Страница 5: ...The standard local temperature sensor has 12 leads and comes installed from the factory A secondary sensor is located internally on the main controller board and serves as a reference and back up sen...

Страница 6: ...Smoke and Generator interface for Controller to function Inputs Lockout 1 2 3 input from HVAC 1 Lockout 2 2 3 input from HVAC 2 Outputs Smoke Fire Form C SPDT Lockout 1 Form C SPDT Refrigerant alarm...

Страница 7: ...ol located in the electrical control panel of the air conditioners being controlled by the lead lag controller To eliminate the 60 second blower off delay disconnect and isolate the wire that is facto...

Страница 8: ...u t a r e p m e T n A F c n o i t a r e p o r e w o l b s u o u n i t n o C h t o B d a e L e n o N e n o N g e d C r o F n i s e t a r e p o m e t s y s r e l l o r t n o C C r o F F t l A e c n e u...

Страница 9: ...conomizer 1st stage cooling set point is the setting SP input into the controller Factory default is 77F 25C On a call for cooling the blower of the lead unit will come on immediately if not already o...

Страница 10: ...default setting user selectable 2 6F warmer than Stage 1 On a call for 2nd Stage cooling the blower of the lag unit is turned on if not already on See Blower Operation and the Stage 2 LED will blink f...

Страница 11: ...operation COOLING OPERATING SEQUENCES FOR NON ALTERNATING LEAD LEAD LAG LAG CONFIGURATION Note Heat pumps cannot be operated in Non Alternating Lead Lead Lag Lag sequence Selecting Heat Pump Yes will...

Страница 12: ...mizer control If outdoor conditions are not acceptable for free cooling the compressor will automatically operate instead of the economizer 4th cooling set point is 2F default setting user selectable...

Страница 13: ...to operate and the compressor will operate on compressor Stage 2 full capacity If the compressor is already operating on Stage 1 partial capacity because outside free cooling range the compressor wil...

Страница 14: ...age should appear For Vista or Windows 7 1 Open Control Panel click Network Internet 2 Click Network Sharing Center 3 Click Local Area Network link 4 Click Properties 5 Highlight Internet Protocol Ver...

Страница 15: ...Alarm b Low Temp Clear or Alarm c High Temp 1 Clear or Alarm d High Temp 2 Clear or Alarm e Controller Failure Clear or Alarm SETPOINTS PAGE Note Read level authority can view this screen but cannot...

Страница 16: ...buttons while the controller is in the normal operating run mode 2 Press and hold the Advance Change Save button and the Up and Down arrow buttons simultaneously for 20 seconds until the display show...

Страница 17: ...o C d r a o B r e w e N T M W N O C E o N r e z i m o n o c E n o i t a c i n u m m o C d r a o B r e w e N T M W N O C E r e z i m o n o c E 0 0 0 4 B C h t i w n o i t a c i n u m m o C d r a o B e...

Страница 18: ...Manual 2100 563C Page 18 of 40 FIGURE 2 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS NO ECONOMIZERS...

Страница 19: ...Manual 2100 563C Page 19 of 40 FIGURE 3 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS NO ECONOMIZER WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 20: ...Manual 2100 563C Page 20 of 40 FIGURE 4 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS NO ECONOMIZERS WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 21: ...Manual 2100 563C Page 21 of 40 FIGURE 5 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS...

Страница 22: ...Manual 2100 563C Page 22 of 40 FIGURE 6 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS...

Страница 23: ...Manual 2100 563C Page 23 of 40 FIGURE 7 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 24: ...Manual 2100 563C Page 24 of 40 FIGURE 8 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 25: ...Manual 2100 563C Page 25 of 40 FIGURE 9 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS...

Страница 26: ...Manual 2100 563C Page 26 of 40 FIGURE 10 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS...

Страница 27: ...Manual 2100 563C Page 27 of 40 FIGURE 11 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 28: ...Manual 2100 563C Page 28 of 40 FIGURE 12 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 29: ...Manual 2100 563C Page 29 of 40 FIGURE 13 CONTROLLERCONNECTIONS HEAT PUMPS NO ECONOMIZER...

Страница 30: ...Manual 2100 563C Page 30 of 40 FIGURE 14 CONTROLLERCONNECTIONS HEAT PUMPS NO ECONOMIZER WITH OPTIONAL ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 31: ...hod to issue an alarm signal that the lead air conditioner is down or not delivering full capacity and that the lag air conditioner is now operating REFRIGERANT PRESSURE ALARMS Air conditioners with J...

Страница 32: ...loose to protect it from possible damage during installation of the wiring to main controller board and or the alarm board It is polarity sensitive and is keyed so it can only be installed in correct...

Страница 33: ...loose to protect it from possible damage during installation of the wiring to main controller board and or the alarm board It is polarity sensitive and is keyed so it can only be installed in correct...

Страница 34: ...wn If no buttons are pushed within thirty 30 seconds the controller will automatically revert back to RUN mode To reset all controller settings to the factory default values press the PROGRAM button f...

Страница 35: ...or 18 3 to 32 2C Default is 77F 25C 5 Deadband between cooling and heating setpoint 2 to 40F or 1 1 to 22 2C Default is 17F 9 4C 6 Continuous blower operation None Lead Both Default is None 7 Degree...

Страница 36: ...Manual 2100 563C Page 36 of 40 FIGURE 17 PARTS LIST DESCRIPTION DIAGRAM MIS 2954 12 9 3 4 5 7 6 11 2 1 10 8...

Страница 37: ...o B m r a l A X X X 3 1 2 0 2 1 6 8 B d r a o B m r a l A X X X 4 2 2 0 2 1 6 8 y a l p s i D m r a l A X X X X X X 5 4 0 3 4 3 1 1 t e k c a r B t r o p p u S X X X X X 6 4 5 8 3 2 5 1 r o o D x o B...

Страница 38: ...Manual 2100 563C Page 38 of 40 This page intentionally left blank...

Страница 39: ...Manual 2100 563C Page 39 of 40 This page intentionally left blank...

Страница 40: ...Manual 2100 563C Page 40 of 40 This page intentionally left blank...

Отзывы: