Programmable Safety Controller SCR P
162
www.bernstein.eu
- Tel: + 49 571 793 0
Figure 120: TIA - Ethernet Addresses
9.7 Temperature, Voltage, and Distance Conversion Information
Download an AOI from
to insert into the PLC program to perform the conversions from the obtained
values to the real values.
9.7.1 Supply Voltage
To obtain the actual voltage reading from the ADC value sent to the PLC, multiple the ADC value by 0.1835.
Supply Voltage = ADC Value × 0.1835
9.7.2 Internal Temperature
First, shift the ADC value left by 2 bits. Then, convert the binary reading into a number. If the number matches an ADC value
in the following table, read the temperature. If the number is between the readings in the table, use the following formula to
obtain the actual temperature.