![Banner SCR P Series Скачать руководство пользователя страница 50](http://html1.mh-extra.com/html/banner/scr-p-series/scr-p-series_instruction-manual_3773339050.webp)
Programmable Safety Controller SCR P
50
www.bernstein.eu
- Tel: + 49 571 793 0
6.8 Status Outputs
6.8.1 Status Output Signal Conventions
Note:
You cannot use the safety outputs as status outputs in the SCR P.
There are two signal conventions selectable for each status output: "PNP On" (sourcing 24 V dc), or "PNP Off" (non-
conducting). The default convention is Active = PNP On.
Table 1: Status Output Signal Conventions
Function
Signal Conventions
Active = PNP On
Active = PNP Off
Status Output State
Status Output State
+24 V dc
Off
Off
24 V dc
Bypass
Bypassed
Not Bypassed
Bypassed
Not Bypassed
Mute
Muted
Not Muted
Muted
Not Muted
Output Delay In Progress
Delay
No Delay
Delay
No Delay
Track Input
Run
Stop
Run
Stop
Track Input Fault
Fault
Ok
Fault
Ok
Track Any Input Fault
Fault
Ok
Fault
Ok
Track Input Group
Initiated Stop
Other Input Caused Stop
Initiated Stop
Other Input Caused Stop
Track Output
SO On
SO Off
SO On
SO Off
Track Output Fault
Fault
Ok
Fault
Ok
Track Output Fault All
Fault
Ok
Fault
Ok
Track Output Logical State
Logically On
Logically Off
Logically On
Logically Off
Track Function Block State
Run
Stop
Run
Stop
Waiting for Manual Reset
Reset Needed
Not Satisfied
Reset Needed
Not Satisfied
System Lockout
Lockout
Run Mode
Lockout
Run Mode
6.8.2 Status Output Functionality
SCR P:
Up to four convertible inputs may be used as a Status Output.
Status Outputs can be configured to perform the following functions:
Bypass
Indicates when a particular Safety Input is bypassed.
Mute
Indicates a muting active status for a particular mutable Safety Input:
• On when a mutable input is muted
• Off when a mutable input is not muted
• Flashing when the conditions to start a mute-dependent override exist (an inactive muting cycle, the
mutable Safety Input is in the stop state, and at least one muting sensor is in the stop (blocked) state); not
available for Virtual Status Output
• On during an active mute-dependent override function (not a bypass function) of a mutable Safety Input
Output Delay In Progress
Indicates if either On- or Off-Delay is active.