9 Industrial Ethernet Overview
9.1 Configuring the Safety Controller
Make sure that
Enable Network Interface
is selected, and the network settings are configured as needed by the chosen
protocol.
1. Connect the Safety Controller to your PC via the USB cable to enable the port.
2. Open the BERNSTEIN Safety Controller Software.
3. Click
Network Settings
.
4. Select the
Enable Network Interface
checkbox.
5. Configure the IP Address and Subnet Mask as needed for your network.
Note:
If a Virtual Reset or Cancel Delay is used, an Actuation Code must be defined and then sent
to the Safety Controller.
6. Click
Send
.
7. Click on the
Advanced
arrow to configure the Advanced network settings, if desired.
The following are the default values for the Safety Controller's Ethernet port and Industrial Ethernet options.
8. Provide the appropriate password to change the configuration and network settings for the Safety Controller.
9. Make sure the Safety Controller has a valid and confirmed configuration file.
The Ethernet port is enabled.
Figure 99: Default Values