![Banner SCR P Series Скачать руководство пользователя страница 21](http://html1.mh-extra.com/html/banner/scr-p-series/scr-p-series_instruction-manual_3773339021.webp)
Programmable Safety Controller SCR P
www.bernstein.eu
- Tel: + 49 571 793 0
21
Input Circuit
Input Signal COS Timing Rules
Stop State
—SO turns Off
when
4
:
Run State
—SO turns On
when
5
:
Dual-Channel A and B Complementary
2 Terminals
3 Terminals
2 Terminals, PNP
24V
ON
OFF
At least 1 channel (A or B) input is in the
Stop state.
Simultaneous:
A and B are both in the
Stop state and then both switch to the Run
state within 3 seconds before outputs turn
On.
Concurrent:
A and B concurrently switch
to the Stop state, then both switch to the
Run state with no simultaneity to turn
outputs On.
Dual-Channel A and B
2-Ch, 2 Terminals 2-Ch, 3 Terminals
2-Ch, 4 Terminals
2-Ch, 2 Terminal
PNP
24V
ON
ON
2X Complementary A and B
4 Terminals
5 Terminals
24V
PNP
ON OFF ON OFF
At least 1 channel (A or B) within a pair of
contacts is in the Stop state.
Simultaneous:
A and B are concurrently
in the Stop state, then the contacts within
a channel switch to the Run state within
400 ms (150 ms for two-hand control),
both channels are in the Run state within
3 seconds (0.5 seconds for two-hand
control).
Concurrent:
A and B are concurrently in
the Stop state, then contacts within a
channel in the Run state within 3 seconds.
There is no simultaneity requirement
between the switching of channel A and
channel B.
4-Wire Safety Mat
2-Ch, 4 Terminals
One of the following conditions is met:
• Input channels are shorted
together (normal
operation)
• At least 1 of the wires
is disconnected
• One of the normally low
channels is detected
high
• One of the normally
high channels is
detected low
Each channel detects its own pulses.
Signal Debounce Times
Closed-to-Open Debounce Time (from 6 ms to 1000 ms in 1 ms intervals, except 6 ms to 1500 ms for mute
sensors).
The closed-to-open debounce time is the time limit required for the input signal to transition from the high
(24 V dc) state to the steady low (0 V dc) state. This time limit may need to be increased in cases where high-
magnitude device vibration, impact shock, or switch noise conditions result in a need for longer signal transition times.
If the debounce time is set too short under these harsh conditions, the system may detect a signal disparity fault and
lock out. The default setting is 6 ms.
Open-to-Closed Debounce Time (from 10 ms to 1000 ms in 1 ms intervals, except 10 ms to 1500 ms for mute
sensors).
The open-to-closed debounce time is the time limit required for the input signal to transition from the low (0 V DC)
state to the steady high (24 V DC) state. This time limit may need to be increased in cases where high magnitude device
vibration,
4 Safety Outputs turn Off when one of the controlling inputs is in the Stop state.
5 Safety Outputs turn On only when all of the controlling inputs are in the Run state and after a manual reset is performed (if any safety inputs
are configured for Manual reset and were in their Stop state).
CAUTION: Debounce and Response
Any changes in the debounce times may affect the Safety Output response (turn Off) time.
This value is
computed and displayed for each Safety Output when a configuration is created.