Programmable Safety Controller SCR P
76
www.bernstein.eu
- Tel: + 49 571 793 0
Muting Block
Default Nodes
Additional Nodes
Notes
IN
MP1
ME
BP
MP2
Muting Sensor Pair input blocks must be connected directly to the Muting function block.
There are five Mute Function types listed below. The following timing diagrams show the
function detail and sensor/safeguarding state change order for each mute function type.
Mute Function Block
One Way - 1 Mute Sensor Pair
Two Way - 1 Mute Sensor Pair
One Way - 2 Mute Sensor Pair
Two Way - 2 Mute Sensor Pair
Two Way - 1 Mute Sensor Pair
Figure 55: Muting Block
—Function Types
There are 2 types of Mute Bypass:
▪
Mute Dependent Override
▪
Bypass (normal)
In the Mute Block Properties menu in the Advanced
settings, if the Bypass check box is checked, the option
to select a Bypass or a Mute Dependent Override is
possible.
The Mute Dependent Override is used to temporarily
restart an incomplete mute cycle (for example after the
mute time limit expires). In this case, one or more mute
sensors must be activated while the safeguard is in the
Stop state.
The normal Bypass is used to temporarily bypass the
safeguarding device to keep on or turn on the output of
the function block.
Figure 56: Muting Block
—Bypass/Override Mode Options