6.

 

TROUBLESHOOTING 

This section provides troubleshooting recommendations for the Advanced Controller system and its 
components when installed, operated and maintained in accordance with Banlaw guidelines. 

ADVANCED CONTROLLER TROUBLESHOOTING GUIDE 

ISSUE 

MEANING 

CHECKS 

SOLUTION 

No fuel dispensed 
Controller display black 
or display does not 
change 

Power outage 

Check main power circuit 
breaker. 
Check power to pump. 
Check ball valve actuation. 

Maintenance to restore 
power 
Restore Power to pump 
Restore ball valve 
operation. 

No power outage 

Check Controller power 
supply. 
Controller PC has the power 
led on. 
Controller screen is on. 

If your site allows manual 
transactions, first attempt a 
manual transaction using a 
level one PIN.  
Failing this, the system 
should be placed into 
override by switching on 
the override Circuit Breaker 
in the ResTrack Controller 
Control Box.  
This power up the nozzle 
enable relays and allows 
refuelling.  
Note: security is 
compromised when the 
Controller is in override. 
Automatic fuel transactions 
will still be recorded whilst 
the ResTrack Controller is in 
override. However, Vehicles 
not registered can fuel as 
well and will create 
transactions with unit as 
OTHER. 

No Fuel Dispensed 
Nozzle is connected 
and machine is 
identified, 
authorisation to 
proceed is displayed 
on the Controller 
Display and Nozzle is 
enabled, but no fuel is 
being delivered 

Control valve actuator is 
not opening 

Check that the control valve 

is in the “Open” position. 

 

If the electrical actuator 
fails to open, check wiring is 
secure.  
Check the relay in the 
control box that energises 
the control valve is 
functioning. This is denoted 
by a yellow illuminated LED.   

Repair replace faulty parts. 

Pump circuitry has tripped 
out. 

Check pump circuitry. 

If necessary, reset pump 
circuit breakers. 

No flow is being detected. 

Check FTP Led state. 
Cycle power to Controller. 

Reload/Update FTP 
firmware (*BANLAW). 
Cycle Controller power. 
 

Содержание ResTrack BFTAC Series

Страница 1: ...tify asset liquid cost profiles While the controller may be used for a range of industrial liquids this document willin the main refer to hydrocarbon fuels The Advanced Controller is the key device to...

Страница 2: ...el cabinet door latch may be locked with an 8 mm shackle padlock The system is capable of controlling and monitoring fluids from delivery via control valves and pumps to storage tanks Accuracy of flui...

Страница 3: ...only to authorised machines vehicles operators Automatic recording of fluid deliveries and fluid dispensing Accurate fluid metering with temperature correction Secure dispensing of fluids only to auth...

Страница 4: ...e you have the latest version of this document Figure 4 Banlaw ResTrack Cabinet Typical configuration The ResTrack Controller has an industrial PC at the core Figure 5 illustrates where important conn...

Страница 5: ...ADER 1 NONE Not required Based on site requirements and preferences 2 CARDAX Gallagher Cardax reader installed 3 HID HID PROXPRO reader installed NUMBER OF FTPs 1 1 off One Fluid Transfer Point interf...

Страница 6: ...an assessment deems the Banlaw product s to be suitable the customer or end user shall ensure effective change management applies should any prominent or influential aspect of the application upon whi...

Страница 7: ...ch Screen Size 35 5cm 14in 22 cm 8 7in for Service Trucks USB USB 2 0 and 3 0 Operation Temperature Range 25 to 50 C 13 to 122 F Certification RCM Cabinet Material Composition Stainless Steel Dimensio...

Страница 8: ...be reported on in the future while showing flow totals and tank levels locally to users The appropriate care should be taken to position the Advanced Controller out of direct sunlight This can only h...

Страница 9: ...d parts Make a general arrangement of where the Controller will be fixed and all associated components Make an assessment of where the hoses can stretch to and fall naturally Make sure the Advanced co...

Страница 10: ...stem response Verify the FTP cards are powered up and the configuration is corrected using the DIP switches and the led states Make sure that the API table is downloaded to the FTP cards if temp compe...

Страница 11: ...action refuelling a unit with the Banlaw ResTrack Advanced controller Equipment that is damaged leaking or otherwise unfit for operation must not be used Maintenance should be carried out to replace o...

Страница 12: ...o ID Refuelling Step Instruction 1 Move the unit into the fuelling area 2 Halt the vehicle as required by site procedures 3 Remove the receiver dust cap 4 Using a clean rag thoroughly clean the receiv...

Страница 13: ...d remove the splash fill nozzle and turn OFF pump and place nozzle on holster or bowser ResTrack will now detect zero fuel flow and after 30 seconds will close the fuel line actuator The volume dispen...

Страница 14: ...his document Figure 11 Manual Delivery Screen Step 2 Select the correct nozzle number then the NEXT button Figure 12 Manual Delivery Screen Step 3 The transaction has now started Open the fuel valves...

Страница 15: ...parts are used for product repair servicing Repairs are carried out by unauthorised personnel Any attempt is made to repair service a product deemed as non serviceable by Banlaw Products are subjected...

Страница 16: ...Controller Keep the Touch screen clean Avoid operating the Touch Screen with dirty fingers PPE and or clothing contaminated with fuel Keep the Advanced Controller cabinet clean and closed all the tim...

Страница 17: ...verride by switching on the override Circuit Breaker in the ResTrack Controller Control Box This power up the nozzle enable relays and allows refuelling Note security is compromised when the Controlle...

Страница 18: ...ng from pulse to Controller board Check Pulse drive mechanism and flow meter Pump may be cutting out due to restriction in flow or problem with pump circuit Check filters for obstruction Pump circuit...

Страница 19: ...To provide further assurance our products and services are backed by generous warranties The Banlaw ResTrack Controller is a fully serviceable product with a serial number and traceable build history...

Страница 20: ...LAW PRODUCT DATA SHEET RESTRACK ADVANCED CONTROLLER Doc ID PRH FMG 21 Version 1 0 Page 20 of 20 Please ensure you have the latest version of this document Liquid Asset Intelligence Website www banlaw...

Отзывы: