3.3
Commissioning
The commissioning process comprises of in depth system documentation and procedures that are
mentioned in this document but are just in guide form.
The commissioning process of the Advanced Controller is as follows. It is meant for systems that have
passed all installation checks and are in an energised state.
•
Check that the cabinet is not dented and clean on the inside. All glands are installed firmly, and blanks
installed.
•
Ensure all electrical cables are well connected and the inside of the Advanced Controller is neat and
tidy.
•
Check terminal numbers correspond to those inserted into the terminals.
•
Nameplate installed with all the client, site and Controller information.
•
Power supply output voltage is correct.
•
The Advanced Controller screen should be powered up.
•
Verify the touch-screen is working properly. Press each key on the screen, traversing menus and
entering pin and unit data and check if each key click produces a system response.
•
Verify the FTP cards are powered up and the configuration is corrected using the DIP switches and
the led states. Make sure that the API table is downloaded to the FTP cards if temp compensation is
to be used.
•
Verify card readers are operation. Swipe a card and validate the correct function of a user
identification and the PIN.
•
Verify iButton operation. Validate the unit identification.
•
Verify Splash-fill and Nozzle Auto-ID operation:
o
Connect Auto-ID DryBreak nozzle to registered Auto-ID receiver.
o
Place Auto-ID Splash-fill nozzle near registered Auto-ID tag.
•
Communication verified with ResTrack Advanced Controller:
o
Check if the Controller is visible via the site network and in the ResTrack web server.
o
Correct information showing, Controller, storages and transactions.
•
Communication verified between the ResTrack Advanced Controller and the Tank Level Devices:
o
Receiving values from temperatures and levels sensors.
o
Correct tank and ullages displayed for each tank.
o
Probe level matches the dip level.
•
Any third-party equipment configured and tested.
•
With the power switched on use the override switch to determine the ball valves actuate correctly.
•
Check the flow meters are reading correctly and schedule calibrations.
•
Complete all commissioning documentation.
•
Complete client sign off.