Masoneilan SVI II ESD Quick Start Guide
=
|
95
Distributed Control Systems Configurations
This section gives guidance for configuration in a DCS application. Figure 25 gives two general-
ized drawings that cover DCS applications to ensure switch safety.
Figure 25 DCS Switches Wiring Options
Configuration Considerations
A typical value for 24 AWG cable about 0.025 Ohm/ft (see Wiring Option #1)).
If IS barrier is a combination of fuse, resistor and Zener diode then the
connection is shown in Option #2. The barrier must have adequate
resistance to limit inrush current, as the fuse cannot limit inrush current (see
Wiring Option #2).
Power source requirements:
V
30 V. I
max
1 A.
SVI
Switch
Resistance
≥
30 Ohms +
wire resistance.
+
-
Negative switch pole
must be
directly wired to negative power supply.
+
-
Wiring Option #1
SVI
Switch
Resistance = Sized so that
circuit is limited < 50 mA
in-rush current.
+
-
Any load (no direct connection).
+
-
Wiring Option #2
Power source requirements:
V
30 V. I
max
1 A.