SVI II ESD Maintenance
Repair and Replacement
Repairs may be made only by authorized personnel trained to repair Safety Devices.
CAUTION
When working on safety rated equipment appropriate risk
reduction safety measures must be in place.
1. A conservative approach is taken in estimating the service interval for the digital
valve controller in Safety Instrumented Systems. For SIS applications, perform
preventive maintenance on the SVI II ESD after five years from the shipment date,
if the average daily ambient temperature is below 60° C (140° F). Where ambient
temperature exceeds 60° C (140° F) for extended periods, reduce this
maintenance interval based on plant experience.
2. SVI II ESD preventive maintenance consists of replacing gaskets, O-rings in the
device and a visual inspection of moving components to verify satisfactory
condition. Following maintenance, the SVI II ESD must be reinstalled on the valve
actuator and calibrated per the procedures in this Quick Start Guide or in the
SVI II
ESD Instruction Manual SIL3
,
GEA18946
. After calibration, validate the SVI II ESD
functional safety. All maintenance procedures must be performed only by
authorized personnel trained to repair Safety Devices.
3. If alarms or alerts are detected during operation, maintenance or periodic
inspection and test, immediately take corrective action according to the
troubleshooting and repair procedures given in the Instruction Manual.
4. The tools required for repair of the SVI II ESD are also listed in the
SVI II ESD
Instruction Manual SIL3
,
GEA18946
.
Factory Notification
Report any failures detected that compromise functional safety to the factory. Contact your local
service representative. Sales Office locations are listed on the back cover of this document.
NOTE
GE does not assume responsibility for the selection, use, or
maintenance of any product. Responsibility for proper selection,
use of any GE’s Masoneilan product remains solely with the
purchaser and end-user. The SVI II ESD requires recertification,
which must be performed by GE authorized personnel trained to
repair Safety Devices.
The contents of this publication are presented for informational purposes only, and while every
effort has been made to ensure their accuracy, they are not to be construed as warranties or
guarantees, express or implied, regarding the products or services described herein or their use
or applicability. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Содержание Masoneilan SVI II ESD
Страница 4: ...This page intentionally left blank...
Страница 8: ...This page intentionally left blank...
Страница 20: ...This page intentionally left blank...
Страница 72: ...This page intentionally left blank...
Страница 92: ...This page intentionally left blank...