Masoneilan SVI II ESD Quick Start Guide
=
|
83
Doc Number ES-727
Revision
W
PDR ECO-
0029774
11/15/2017
Written By
P.Levesque
13DEC2006
Checked
T.Kabir
10JAN2007
Filename
ES-727.DOC
Page 5 of 13
Approved
T. Kabir
10JAN2007
Copyright 2017 as an unpublished trade secret. This document and all information herein is the property of
Dresser LLC.
It is confidential
and must not be made public or copied and is subject to return upon demand.
5.2
Cable Glands
Certified cable glands are required based on the hazardous area the device is installed in. That is, the
particular cable gland used must have the same certification as the tick-box checked off on the label (See
Section 6, Figure 1).
5.3
Bolting
“X” Marking on label
- M8 X 1.25-6g cover screws must be supplied by Masoneilan.
No substitution allowed. Minimum yield stress to be 296 N/mm^2 (43,000 psi)
5.4
Carbon Disulphide Exclusion
Carbon Disulphide is excluded.
(IEC 60079-1, Clause 15.4.3.2.2., carbon disulphide is excluded for enclosures with a volume greater
than 100cm
3
)
5.5
Electrostatic Discharge
"X" Marking on label
- Potential Electrostatic Charge Hazard
–
For safe operation use only wet cloth
when cleaning or wiping device, and only when local conditions around the device are free of potentially
explosive atmospheres. Do not use dry cloth. Do not use solvent.
5.6
Dust
"X" Marking on label
- Instruments installed in dusty hazardous areas, Zones 20, 21 and 22; must be
cleaned regularly to prevent the buildup of dust layers on any surface. To avoid the risk from
electrostatic discharge, you must follow the guidance as detailed in EN TR50404. For safe operation,
use only wet cloth when cleaning or wiping the device. Cleaning must only be done when local
conditions around the device are free of potentially explosive atmospheres. Do not use dry cloth or any
solvents.
6
INTRINSICALLY SAFE REQUIREMENTS
6.1
DIV 2 (No I.S. Barrier)
WARNING: EXPLOSION HAZARD
–
Do not disconnect equipment unless power has been switched
off or the area is known to be non-hazardous.
6.2
Category II (Zone 0)
For operation in hazardous area Category II 1, over-voltage protection of the electrical connections needs
to be installed according to EN 60079-14
For operation in hazardous area Category II 1 the ambient temperature needs to be lowered according to
the requirements of EN 1127-1 (reduction factor of 80%). The maximum allowed ambient temperature
for Category 1 inclusive the requirement of EN1127-1 is:
T6: Ta = -40°C to +43°C