Installing the SVI II ESD Display Cover
The replacement Display Cover is shipped with a lanyard to prevent the cable (that connects
from the display to the Terminal Board) from breaking. Insert the lanyard under the screw in the
lower left corner that attaches the terminal board to the SVI II ESD housing.
To install the cover:
1. Install the lanyard and tighten the screw to 5 in/lb.
2. Using a 3 mm hex key, remove the screw from the lower left corner, connecting
the terminal board to the SVI II ESD housing.
3. Connect the cable from the display into the LCD connector on the terminal board.
4. Ensure that the gasket is in its groove in the housing.
5. Place the cover over the screw mounts.
6. Tighten the four screws with the 5 mm hex key.
7. After installing the new display
“Powering Up the SVI II ESD” on page 44.
NOTE
The cover of the SVI II ESD is a critical component for safety in
Hazardous Areas. To ensure safe operation the flat surfaces of the
cover and the housing must be clean and absolutely free of
particles or dents. There must be no gap between the housing
and cover; torque spec is 50 in/lb.
Ensure that:
The gasket is seated in the groove in the housing flange.
No wires or retaining cable can be trapped under the cover flange.
The flange area is not corroded and the surface is not scarred.
The four cover bolts are securely tightened to 50 in/lb.