© 2018 Baker Hughes, a GE company, LLC. All rights reserved.
66 |
=
BHGE
Calibration
WARNING
In order to calibrate the SVI II ESD, it must be in SETUP mode.
To calibrate the SVI II ESD:
1. On power up if the SVI II ESD is not in NORMAL mode, switch to NORMAL mode.
The display alternates between
POS
and
SIGNAL
indicating NORMAL mode.
2. Press
+
to access
MANUAL
mode.
3. With
MANUAL
mode displayed, press
*
to select the MANUAL mode the display
alternates between
POS –M
and
SIG
indicating MANUAL mode.
4. Press
*
and
SETUP
appears.
5. Press
*
again;
CONFIG
appears.
6. Press
+
to display
CALIB
.
7. Select
CALIB
by pressing
*
.
STOPS
appears.
8. Press * to activate the Find Stops calibration procedure.
The valve moves full open and back to full closed.
9. Observe all warnings.
10. Press
*
to cause the valve to stroke and to automatically calibrate valve travel.
11. After the STOPS procedure finishes, press
+
twice until
TUNE
appears.
Содержание Masoneilan SVI II ESD
Страница 4: ...This page intentionally left blank...
Страница 8: ...This page intentionally left blank...
Страница 20: ...This page intentionally left blank...
Страница 72: ...This page intentionally left blank...
Страница 92: ...This page intentionally left blank...