© 2018 Baker Hughes, a GE company, LLC. All rights reserved.
64 |
=
BHGE
Configuration with Pushbuttons
To change the current configuration parameters:
1. On power up if the VI II ESD is not in NORMAL mode, switch to NORMAL mode. The
display alternates between
POS
and
SIGNAL
indicating NORMAL mode.
2. Press
+
to access MANUAL mode.
3. With MANUAL mode displayed, press
*
to select the MANUAL mode the display
alternates between
POS –M
and
SIG
indicating MANUAL mode.
4. Press
*
and
SETUP
appears.
5. Press
*
again;
CONFIG
appears.
6. Press the
*
button to access the
CONFIGuration
menu.
7. Set the configuration parameters:
Air Action, Air Pressure Units
and
Language
. For
each parameter:
a. Press
*
to access and change the parameter.
b. Press
+
to move to the next parameter.
c. Press
+
to return to SETUP.
d. Press
+
to return to NORMAL mode.
Содержание Masoneilan SVI II ESD
Страница 4: ...This page intentionally left blank...
Страница 8: ...This page intentionally left blank...
Страница 20: ...This page intentionally left blank...
Страница 72: ...This page intentionally left blank...
Страница 92: ...This page intentionally left blank...