INTRODUCTION
SPECIFICATIONS
1 - 8
WBPEEUI110505A0
Measurement range,
turndown ratio, zero
suppression, and zero
elevation
Lower range value (zero) and upper range value (100%) can be calibrated at any
value of pressure, provided that:
1. Their algebraic difference (the calibrated span) corresponds to an
authorized TDR.
2. Both are within the following acceptable limits.
Reference accuracy -
per IEC 770 and SAMA
PMC 31.1
The reference accuracy includes the effects of linearity, hysteresis, repeatability,
and deadband. This value is for transmitters with zero based spans, silicone oil fill,
and Hastelloy C-276 isolating diaphragms at a reference temperature of 25°C
(77°F). The value listed may vary depending on the URL and calibrated span of the
particular transmitter.
±0.20% of span or ±
(% of span), whichever is greater.
Stability per 12-month
period
±0.25% of URL at reference conditions
Temperature limits
Table 1-3. Specifications
(continued)
Property
Characteristic/Value
Type
International System Units
Range Limits
(kPa)
Span and Turndown Ratio (TDR)
Upper
Lower
Nominal (kPa)
Maximum (kPa)
Minimum (kPa)
PTSDLC
30
-30
30
1:1 TDR
60
0.5:1 TDR
5
6:1 TDR
PTSDLD
90
-90
90
1:1 TDR
180
0.5:1 TDR
5
18:1 TDR
PTSDLF
500
-500
500
1:1 TDR
1,000
0.5:1 TDR
25
20:1 TDR
Type
American Units
Range Limits
(in. H
2
O)
Span and Turndown Ratio (TDR)
Upper Lower
Nominal
(in. H
2
O)
Maximum
(in. H
2
O)
Minimum
(in. H
2
O)
PTSDLC
120
-120
120
1:1 TDR
240
0.5:1 TDR
20
6:1 TDR
PTSDLD
360
-360
360
1:1 TDR
720
0.5:1 TDR
20
18:1 TDR
—
(psi)
PTSDLF
75
-75
75
1:1 TDR
150
0.5:1 TDR
3.8
20:1 TDR
0.016
URL
×
Span
--------------------------------
Parameter
Electronics
1
Cell
1,2,3
LCD
4
°C
°F
°C
°F
°C
°F
Normal
operating
-40 to +85 -40 to +185
-40 to +85
-40 to +185
0 to +50
+32 to +122
Extreme
operating
-50 to +85 -58 to +185 -50 to +120 -58 to +248
0 to +50
+32 to +122
Storage/
transport
-55 to +85 -67 to +185
-55 to +85
-67 to +185 -20 to +70
-4 to +158