OPERATING PROCEDURES
OPERATIONAL FUNCTIONS
5 - 6
WBPEEUI110505A0
Output Key
Press the OUTPUT key on the Type STT terminal and follow
the procedures in the
Type STT Smart Transmitter Termi-
.
MONITOR OUTPUT
The Type PTSDL level transmitter output can be monitored by
pressing the OUTPUT key on the Type STT terminal, and
choosing
MONITOR OUTPUT
from the display menu (refer to
the
Type STT Smart Transmitter Terminal Instruction
The output displays as a percent, rather than in milliamperes,
and updates once per second.
MONITOR INPUT
The input to the Type PTSDL level transmitter can be moni-
tored by using the OUTPUT key on the Type STT terminal and
selecting
MONITOR INPUT
from the displayed menu (refer to
the
Type STT Smart Transmitter Terminal Instruction
The input displays in engineering units and updates once per
second.
MONITOR CELL TEMPERATURE
By pressing the OUTPUT key on the Type STT terminal and
selecting
TEMPERATURE,
the Type STT terminal displays the
ambient temperature of the cell in degrees Celsius.
MONITOR SECONDARY ENGINEERING UNITS
The secondary engineering units variable can be monitored by
the Type STT terminal by pressing the OUTPUT key and select-
ing
SECONDARY UNITS.
The output reflects the output of the
transmitter, but it is a percentage of the secondary lower and
upper range values and displays in secondary engineering
units.
Example:
If the secondary lower range value is 10.0 gal/hr, the secondary upper range
value is 100.0 gal/hr and the output of the transmitter is at 75 percent, the dis-
play reads 75-percent range or
77.5 GAL/HR.
Status Key
The status of the transmitter, determined from results of the
continuous self-diagnostics, can be checked using the STATUS
key on the Type STT terminal. Refer to
for the correc-
tive action necessary.