4-11
Chapter 4. BASIC OPERATION
Handling Precautions
•
When "0: RUN key disabled" is selected for "
C-02
: RUN key operation and
operating mode selection when power turned ON" in the function setup, the
operating mode is not changed even though the RUN key is pressed.
•
When "operating mode change (5, 6, or 8)" is selected for external contact
input function assignment
C-
10
to
C-
12
in the function setup, changes
by external contact take precedence over RUN key operation. In the same
manner, when "operating mode change (1 or 5)" is selected for external 3-way
switching function
C-09
in the function setup, the external 3-way switching
input takes precedence over the RUN key operation.
•
The fully open mode cannot directly be changed to the control mode. To make
the change, press the RUN key to change the fully open mode to the fully
closed mode. After that, press the RUN key again to change the fully closed
mode to the control mode.
Содержание Micro Flow MQV0002
Страница 46: ......
Страница 68: ......
Страница 69: ...7 1 Specifications Shown on next page Chapter 7 SPECIFICATIONS...
Страница 90: ......
Страница 94: ...Specifications are subject to change without notice 10 1st edition Apr 2006 7th edition Sep 2018 V...