Installation
MagneW
FLEX+/PLUS+
Electromagnetic Flowmeter Detector
2-13
2.4.5: Installation on a horizontal pipe
To install a wafer detector on a horizontal pipe:
Follow this procedure to install the detector on a horizontal pipe.
Step
Action
Drawing
1
•
Insert through-bolts in the flange holes
shown by black dots in the drawing. Slip
two centering nuts onto each through-bolt
before inserting the bolts.
Flange
2
• Turn the detector so that the direction mark
on the detector matches the direction of
fluid flow.
• Insert the detector and gaskets between the
pipe flanges.
• Position the detector so that it sits on top of
the centering.
Gasket
Direction of
fluid flow
3
• Make sure that the detector remains
properly centered.
• Make sure that the gaskets do not protrude
beyond the edges of the pipe flanges.
• When you have checked these items, insert
the remaining through-bolts into the flange
holes and tighten the bolts evenly using the