4.1 - “SEMI-AUTOMATIC CLOSING” MODE
Description of operation from the closed gate
position:
To open the gate:
•
Activate the complete (or partial) opening
command.
• The flashing light will flash (1 flash per second).
• 1 second later, panel M1 starts opening.
• 2.5 seconds later, panel M2 starts opening.
• Both panels open up to their opening stop.
•
When both panels have reached their opening
stop, the flashing light will stop flashing and the
manoeuvre will be complete.
To close the gate:
• Activate the complete or partial opening command.
• The flashing light will flash (1 flash per second).
• 1 second later, panel M2 starts closing.
• A few seconds later, panel M1 starts closing.
• Panel M2 reaches its closing stop.
•
Some time later (2.5 seconds by default, but
this time can be adjusted), panel M1 reaches its
closing stop.
•
The flashing light will stop flashing and the
manoeuvre will be complete.
At any time, you can stop the gate’s movement by
activating a command (total or partial). If you activate
the gate control again, the gate will start in the
opposite direction.
4.2 - “AUTOMATIC CLOSING” MODE
Description of operation from the closed gate
position; the photocells must be operational:
• Activate the complete opening command.
• The flashing light will flash (1 flash per second).
• 1 second later, panel M1 starts opening.
• 2.5 seconds later, panel M2 starts opening.
• Both panels open up to their opening stop.
• 1 second later, panel M2 starts closing.
• A few seconds later, panel M1 starts closing.
• Panel M2 reaches its closing stop.
•
Some time later (2.5 seconds by default, but
this time can be adjusted), panel M1 reaches its
closing stop.
•
The flashing light will stop flashing and the
manoeuvre will be complete.
At any time, you can stop the gate’s movement by
activating a command (total or partial). If you activate
the gate control again, the gate will start in the
opposite direction. If you activate a command during
the time delay, it will be stopped and automatic
closure will be cancelled.
4.3 - “COLLECTIVE” MODE
Operation is identical to “automatic closure” mode,
except:
The photocells must be operational.
• You cannot stop the gate from opening, either with
the complete or partial opening command.
• If you activate the complete opening command
during the time delay, it is reloaded with the initial
time to extend the time before automatic closure.
• If you activate the complete opening command
during closure, the gate will stop and open again
and the time delay before automatic closure will
start.
• The partial opening command is inoperative.
5 - PHOTOCELLS
• During closure, if an object or a person obstructs
the infrared beam between the two photocells, the
gate will stop and start opening again. If automatic
closure is activated, the time delay will start. If at
the end of the time delay, the photocell beam is
cut, the gate will wait for the beam to be released
before closing again. If after 3 minutes, the beam
has still not been released, automatic closure will
be cancelled, the system will go on standby.
• Photocells can also be active at the beginning of
the opening process (this is useful if a second set
of photocells is installed - see “Advanced Settings
(Menu 2)”).
• If this is not the case and the beam is obstructed
when the gate should start to open, the flashing
light will emit double flashes for 30 seconds unless
a command is activated. For the gate to be able
to open, the beam must be unobstructed and a
command must be activated.