EN
31
EN
30
Inner side of the property
view from above
pair 2
pair 1
RX1
RX2
TX1
TX2
In that case, the system must verify that its infrared
beam is not obstructed before starting to open the
panels. But by default, photocells are only tested
during closure.
To activate or deactivate photocells at the
beginning of the opening process, follow the
procedure below
• Press “
PROG
” for 3 seconds. L0 will flash once
and L1 will switch on.
• Press “
PROG
” for 3 seconds. L0 will flash twice.
• Press “
+
” once. L2 will turn on instead of L1.
• Press
OK
.
•
If L1 is off, the photocells are inactive at the
beginning of the opening process. Press “
+
” to
activate them, then
OK
to confirm. All LEDs will
turn on and off to confirm the operation.
• If L1 is on, the photocells are active at the beginning
of the opening process. Press “–” to deactivate
them, then
OK
to confirm. All LEDs will turn on
and off to confirm the operation.
3.2.3 - TYPE OF GATE
To operate the electronic card on a single-panel
gate, this setting must be changed. By default, this
value is set to 0 (two-panel gate mode). In addition,
the motor output that remains active in side gate
mode is M1 (not to be confused with the pedestrian
passage function).
To activate or deactivate this function, follow
the procedure below
• Press “
PROG
” for 3 seconds. L0 will flash once
and L1 will switch on.
• Press “
PROG
” for 3 seconds. L0 will flash twice.
• Press “
+
” twice and L3 will turn on instead of L1.
• Press
OK
.
• If L1 is off, gate mode is activated. Press “
+
” to
activate side gate mode, then
OK
to confirm. All
LEDs will turn on and off to confirm the operation.
• If L1 is on, side gate mode is activated. Press “
–
” to
activate gate mode, then
OK
to confirm. All LEDs
will turn on and off to confirm the operation.
Self-learning is required if this setting is
changed.
3.2.4 - STOP TOLERANCE
During self-learning, the system learns the path of
each panel to determine when a panel stops if it
has reached a stop or an obstacle. In fact, during
a movement, if more than a certain percentage of
the path remains to be completed by the panel but
it comes under strain, the system considers it to
be pushing against an obstacle. If the panel comes
under strain when less than such percentage
remains to be completed, the system considers
that the panel has reached its stop. By default, this
percentage is 3%.
However, the accuracy of the system depends on
many parameters, such as temperature, motor
quality, the type of motor cables and the flexibility
and weight of the gate. Depending on these
parameters, the path measuring system may not
be accurate enough to operate with this default
tolerance. In this case, the system can trigger
obstacle detection when the panels reach their
normal stop. If this occurs (and after confirming
that the opening and closing stops are stable), the
obstacle detection tolerance must be increased.
To adjust this tolerance level, follow the
procedure below
• Press “
PROG
” for 3 seconds. L0 will flash once
and L1 will switch on.
• Press “
PROG
” for 3 seconds. L0 will flash twice.
•
Press “
+
” 3 times. L4 will turn on instead of L1.
• Press “
OK
”, and the number of LEDs lit will then
show the value set.
• Use the “
–
” and “
+
” buttons to change this value.
The higher the value, the higher the tolerance level
(“lower risk of obstacle detection at the stop”).
• Press
OK
to confirm this value. All the LEDs will
turn on and off to confirm the operation.
Self-learning is required if this setting is
changed.
D - BEGINNING OPERATION