background image

EN

27

EN

26

seconds and is 30 seconds by default.

L1

L2

L3

L4

15 s

L1

L2

L3

L4

30 s

L1

L2

L3

L4

45 s

L1

L2

L3

L4

60 s

L1

L2

L3

L4

90 s

2.5 -  MOTOR FORCE

This system controls the force of the motors by 
detecting the maximum current they can absorb. 
As a result, if an obstacle pushes with enough force 
against a gate panel, the motor current exceeds 
the detected value and the gate stops. In most 
cases, it is not necessary to change this setting.

The force is adjustable from 0 to 4 and is set to 3 
by default. 

However, if the force is insufficient, a gust of wind 
may cause one or more panels to stop. 

•  In this case, it is necessary to increase the level of 

force to 4.

•  On the other hand, if the gate has a rather weak 

structure and a low wind load, it is recommended 
that the force be reduced.

Note

To meet the requirements of Standard 12453, 
it may be necessary to change the force of the 
motors.

To adjust the force, follow the procedure 
below

•   Press  “

PROG

” for 3 seconds. L0 will flash once 

and L1 will switch on.

•  Press “

+

” twice and L3 will turn on instead of L1.

•  Press OK, and the number of LEDs that turn on will 

indicate the set force value.

•  Use the “

+

” and “

-

” buttons to change the force 

and confirm with the

 

OK

 

button. All the LEDs will 

switch on and off to confirm the operation.

NOTE: 

 if the force setting is changed, self-learning 

must be repeated.

2.6 -  SPEED

You can adjust the speed by a value of 0 to 4. The 
default speed is 3.
If the gate is too fast, it may be necessary to reduce 
the speed.

To adjust the speed, follow the procedure 
below

•  Press PROG for 3 seconds. L0 will flash once and 

L1 will turn on.

  Press “

+

” 3 times. L4 will turn on instead of L1.

•  Press OK and the number of LEDs that turn on will 

indicate the set value.

•  Use the “

” and “

+

” buttons to change this value.

•  Press OK to confirm this value. All the LEDs will turn 

on and off to confirm the operation.

NOTE:

 

if the speed setting is changed, self-learning 

must be repeated.

2.7 -  SELF-LEARNING

The role of self-learning:

In order for the card to learn which motors are 
connected and the path of the door, self-learning 
must be launched.
In addition, if certain settings are changed (force, 
speed), self-learning must be repeated.

IMPORTANT

•  

The panels must have fixed stops at the end 

of the closing motion (central stop) and at 
the end of the opening motion (side stops), 
during self-learning, and they must not be 
moved or removed afterwards. If the stops 
are not firmly attached to the ground, this can 
lead to self-learning failure.

•  The panels can be in any position (open, closed, 

ajar) before starting the self-learning procedure.

• Prioritise placing the panels in a semi-open 

position to control the motor’s first movement 
(closing)

•  Before launching self-learning, it is vital to check 

for the correct polarity on the motor connections. 
To do this, launch the manual control mode by 
pressing the OK button for 3 seconds. Press 

D - BEGINNING OPERATION

Содержание 114170

Страница 1: ...rka 310 EN Ref 114170 www avidsen com V4 24V OPENING PANEL 2 50M PER PANEL 2 20M MAXIMUM 150KG PER PANEL COMPATIBLE WITH WITH ALL TYPES OF OPENWORK GATES SOLAR OPTION SMARTPHONE COMPATIBLE OPTION PHOT...

Страница 2: ...The mains electricity 19 7 2 Telescopic motors 20 7 3 Flashing light 20 7 4 Photocells optional 21 7 5 Control parts optional 21 7 6 Backup battery optional 22 7 7 Solar power kit optional 22 D BEGIN...

Страница 3: ...ctive mode 35 5 PHOTOCELLS 35 5 1 Obstacle detection 36 6 MANUAL MOVEMENT 36 7 OPTIONAL ACCESSORIES 37 F MAINTENANCE AND UPKEEP 1 MAINTENANCE WORK 38 2 OPERATING INDICATORS 39 2 1 History of events an...

Страница 4: ...es Do not let children play with the gate control devices Keep the remote controls out of the reach of children Avoid any natural obstacles branch stone high grass etc impeding the gate s movement Do...

Страница 5: ...damp cloth Never use an aerosol to spray the product as this may damage the internal workings Do not clean with a pressure washer 4 RECYCLING Disposing of used batteries in household waste is strictly...

Страница 6: ...DGDSWp j O pSDLVVHXU GX SRUWDLO O D SRLQWV GH IL DWLRQ drilling the post flashing light motor attachment to the post electronic panel flashing light attachment of the brackets onto the posts 3m cable...

Страница 7: ...otection Force limiter and 1 pair of photocells to protect the gate s automatic closing The flashing light is an essential safety component The proper operation of the safety devices must be checked e...

Страница 8: ...torised gate as well as the adapted solutions to eliminate those hazards are as follows Subpanels Following installation there may be a shear zone between the panel and the corner of the post In this...

Страница 9: ...ated in direct view of the driven part but away from moving parts Unless it operates with a key it must be installed at a minimum height of 1 5 m and must not be accessible to the public After install...

Страница 10: ...installation of the side stops depends on the desired opening angle which depends on distance D the distance between the axis of the hinge and the inner side of the post D D positive distance D negati...

Страница 11: ...istance D in mm 90 from 0 to 190 max 95 from 0 to 160 max 100 from 0 to 140 max 105 from 0 to 120 max 110 from 0 to 90 max 120 from 0 to 30 max D D central stop Inner side of the property view from ab...

Страница 12: ...distance B which allows you to determine the post mounting bracket position The table also indicates the hole in which the motor will be mounted The height of the centre of the mounting bracket must...

Страница 13: ...If the post is made of metal we recommend welding or passing the threaded rods through to secure them with self locking nuts Consult a professional if in doubt Attaching the gate bracket to the motor...

Страница 14: ...er tube as shown in the drawing below 20mm tube int rieur 20mm Screw the 20 mm inner tube back on using the previously made mark push the tube in until the mark disappears but no further 20mm tube int...

Страница 15: ...hich the switchgear is attached and must be visible both inside and outside Only use the light provided in the kit 24 V 2 W The flashing light may be fastened on the wall with or without support With...

Страница 16: ...switchgear The surface of the posts must be perfectly flat in order to properly align the infrared beam of the photocells Place the photocells at exactly the same height from the ground they must be...

Страница 17: ...f the property 30cm min 60cm max view from above Inner side of the property perfect alignment 10cm min 15cm max Outer side of the property Outer side of the property Outer side of the property 45mm 20...

Страница 18: ...able is 80 cm deep with red warning mesh or the cable is run through a sheath vers 230V Safety instructions All electrical connections must be performed with the power switched off safety switch in OF...

Страница 19: ...in 16A max and a differential device 30mA It must be compliant with the applicable electrical safety standards The 230V power cable must be HO5RN F type Connect the wires from the power supply and mak...

Страница 20: ...L2 L3 L4 BAT TRANS GND GND PHO 24V M1 M2 M1 M2 warn warn 2B M2 M1 The motor that opens first must be connected to the M1 output of the electronic card Black Red 7 3 FLASHING LIGHT Connect the flashing...

Страница 21: ...M1 M2 warn warn 2B NO COM NC With 2 sets of photocells remove the connector between GND and PHO BAT TRANS GND GND PHO 24V M1 M2 M1 M2 warn warn 2B NO COM NC NO COM NC photocell RX1 photocell TX1 phot...

Страница 22: ...LAR POWER KIT OPTIONAL Warning do not connect a solar power supply at the same time as the mains power supply The 24V solar power kit is plugged into the same connector as the backup battery The solar...

Страница 23: ...or 3 times and only the green LED should be switched on When the user performs no action on a button for 15 seconds the system automatically goes back to MENU 0 2 BASIC SETTINGS MENU 1 2 1 MENU STRUCT...

Страница 24: ...0 r glable de 0 4 MODE 1 pas de fermeture auto MODE 2 fermeture auto MODE 3 mode collectif force des moteurs mode de fonctionnement temps de temporisation 0 15 sec 1 30 sec par defaut 2 45 sec 3 60 s...

Страница 25: ...gate or pedestrian command Collective mode mode 3 This mode is used for a collective access gate Closed gate pressing and releasing the gate command once opens the gate which remains open for a certa...

Страница 26: ...SPEED You can adjust the speed by a value of 0 to 4 The default speed is 3 If the gate is too fast it may be necessary to reduce the speed To adjust the speed follow the procedure below Press PROG for...

Страница 27: ...lly accelerating The panels reach the central stop with a difference of 2 5 seconds or more depending on the setting see MENU 3 Error during self learning If self learning does not work as described a...

Страница 28: ...button for memorisation If the red LEDs all turn on for 1 second this means that memorisation is successful If the red LEDs all flash 3 times this means that the system has waited for more than 10 se...

Страница 29: ...essary in the event of a problem or for specific use of the electronic card There are two additional menus with basic settings r glages simples MODE TEMPORISATION FORCE VITESSE r glages simples Acc l...

Страница 30: ...L3 L4 Enregistre r glage L1 L2 L3 L4 Enregistre r glage L1 L2 L3 L4 This change requires a new self learning procedure 3 2 1 ACCELERATION The acceleration at the start of the panel opening process can...

Страница 31: ...ess to activate gate mode then OK to confirm All LEDs will turn on and off to confirm the operation Self learning is required if this setting is changed 3 2 4 STOP TOLERANCE During self learning the s...

Страница 32: ...posed to the wind panel M2 may be stopped by the wind and panel M1 may be helped by the wind on closing In this case panel M1 may catch up to panel M2 and the panels may close in the wrong order If th...

Страница 33: ...this time to 3 seconds To set the pre flashing time follow the procedure below Press PROG for 3 seconds L0 will flash once and L1 will switch on Press PROG for 3 seconds L0 will flash twice Press PRO...

Страница 34: ...rol devices Prevent children from playing near or with the motorised gate Do not deliberately stop the moving gate except of course with a control device or for an emergency stop Prevent any natural o...

Страница 35: ...he flashing light will stop flashing and the manoeuvre will be complete At any time you can stop the gate s movement by activating a command total or partial If you activate the gate control again the...

Страница 36: ...If the gate has a large area of wind resistance this can trigger obstacle detection in windy weather In this case increasing the motor force is recommended 6 MANUAL MOVEMENT In order to manually mano...

Страница 37: ...EN 37 E USE Backup battery Photocells Additional remote controls Gate video intercom system Connected module Coded keypad Solar kit 7 OPTIONAL ACCESSORIES photo not contractually binding...

Страница 38: ...incorrect positioning of the lid the holes made to run the cable or an incorrectly positioned grommet can damage the product Any trace of infiltration must be eliminated if silicone is used do not use...

Страница 39: ...plus r cent au plus ancien MENU 0 derni re erreur L1 L2 L3 L4 L1 L2 L3 L4 L1 L2 L3 L4 L1 L2 L3 L4 historique des v nements L1 L2 L3 L4 OK 2 1 HISTORY OF EVENTS AND ERROR CODES During operation events...

Страница 40: ...en reached Check that the motor is engaged E Panel M1 closed before panel M2 Increase the time interval between the movement of both panels E Three obstacles detected in a row during opening Check the...

Страница 41: ...unobstructed If a wired control device is connected to input 2B LED L2 turns on when the contactor of the component is activated 2 3 TOTAL RESET You can reset to factory settings To do so press and a...

Страница 42: ...EN 42 2 5 REPLACING THE POWER FUSE Switch the motor drive off Use a 250V 5A time delay fuse F MAINTENANCE AND UPKEEP...

Страница 43: ...erating temperature 20 C 60 C Protection rating IP44 ELECTRONIC CONTROL BOX Type Electronic control box for 2 x 24 VDC motors Contents 1 AVLO electronic card 1 x 230 24 VAC transformer Power supply 23...

Страница 44: ...controlled by the electronic card Power supply Max supply voltage 24 VDC Operating temperature 20 C 60 C Protection rating IP44 REMOTE CONTROL Type Type OOK AM modulation 16 bit Rolling code encoder i...

Страница 45: ...e team technicians 0 892 701 369 Monday to Friday 9pm to 12pm and 2pm to 6pm 4 PRODUCT RETURNS AFTER SALES SERVICE If despite the care we have taken in designing and manufacturing your product it need...

Страница 46: ...Avidsen 19 avenue Marcel Dassault ZAC des Deux Lions 37200 Tours France...

Отзывы: