background image

1

 Instructions for installation & use

Toll free helpline

Please have your serial number and
model name available before calling.
Australia 1800 638 234
New Zealand 0800 653 667
United Kingdom 0800 073 0112
www.merlingo.com

G815D

remote control openers
security at your fingertips

 swing gates

residential gate opener for 

Содержание G815D

Страница 1: ...ease have your serial number and model name available before calling Australia 1800 638 234 New Zealand 0800 653 667 United Kingdom 0800 073 0112 www merlingo com G815D remote control openers security...

Страница 2: ...with a switch that prevents the drive from operating when the wicket is open Connect a Normally Closed switch to the STP and GND terminals of the controller board Locate controls carefully Install an...

Страница 3: ...lways disconnect the power supply from the drive before cleaning or maintaining the gate or drive The drive or gate may operate unexpectedly due to other users with remote controls or due to automatic...

Страница 4: ...ired Keep the path of the gate free from debris and foliage The gate and its moving parts may sustain damage or wear presenting additional load to the opener Frequently examine the installation for si...

Страница 5: ...D will blink during learning The controller is ready for another wireless control when the red LED is steadily lit 4 Press P2 RADIO to exit learning mode NOTE The learning procedure will time out afte...

Страница 6: ...the gate The gate hinge pivot points should be perfectly parallel to a plumb line When closed the gate leaves should line up evenly and not bind against each other The leaves should not be damaged or...

Страница 7: ...control wires in the same conduit Low voltage cable sizes Voltage will drop along low voltage cables over long distances It is recommended to use cable with conductors of the following minimum cross...

Страница 8: ...for the weather conditions 6 Keyed switch must be rated suitably for the weather conditions 7 Keypad Merlin M840 wireless optionally with wired power supply 8 Solenoid lock or latch avail for horizont...

Страница 9: ...d This is to reduce the likelihood of dust entering the screw mechanism Position relative to gate pivot Refer to the diagram below for the typical co ordinates of A and B Some guidelines for an easy i...

Страница 10: ...the gate components 150 9 0 100 110 160 180 130 160 190 155 165 converging d i v e r g i n g diverging diverging converging converging converging arm and gate converge at one position but diverge at...

Страница 11: ...nts securely Mounting the actuator to the brackets Use the spacer washers 10 mm bolt and pin provided Setting the limit stops Unlock the manual release and move the gate through the full range of trav...

Страница 12: ...l receivers keypads PE beams ensure the total combined load on the VA and TXF terminals does not exceed 150 mA If necessary remove accessories or provide additional power supplies directly to each acc...

Страница 13: ...r seconds of operation courtesy lamp EXT LAMP electric lock EL LOCK module output To connect an electric lock or a courtesy lamp it is necessary to t an optional expansion module Only one module can b...

Страница 14: ...through a learned wireless remote control If the gate is moving when this terminal is momentarily disconnected from ground then the gate will stop moving until the connection is re established and the...

Страница 15: ...es the application mode must be changed 1 Press P2 RADIO until the red LED is lit 2 Press P1 SET and observe the number of ashes of the yellow LED 1 ash for linear actuators 2 ashes for harmonic actua...

Страница 16: ...is ashing The following steps are performed automatically 1 Detects whether one motor or two is tted 2 Sets pedestrian opening on M1 leaf to half way 3 Checks for presence of photocells or a jumper on...

Страница 17: ...ve seconds and then the board will be ready to operate No memory settings are altered when RESET is pressed No learned wireless transmitters are removed from memory enable testing of safety devices j...

Страница 18: ...rmined by the motor power and the time that the power is applied to the obstruction Motor power is determined by the maximum voltage and maximum current This FOR setting alters the motor voltage The A...

Страница 19: ...sional Setup the above behaviours will be modi ed accordingly PAU full anti clockwise Gate opening stop if the beam is interrupted continue opening when the beam is clear once open the gates will auto...

Страница 20: ...times of between 3 and 30 seconds enable lock strike delay jumper STRIKE If the ELU module is connected along with an electric lock then this jumper may be required When the STRIKE jumper is connected...

Страница 21: ...than to press the P1 SET and P2 RADIO buttons on the controller board If so learn one button for P1 learn the button with the CH RADIO jumper removed and one button for P2 learn the button with the C...

Страница 22: ...Only press P1 SET if Pedestrian Access is required The M1 leaf will begin opening Press P1 SET at the time where the Pedestrian Access wing is at the desired open position The leaf will close fully a...

Страница 23: ...f it is heavy to move by hand Transmitter range is less than normal Your transmitter battery may be going at If you have an external antenna then the wire may be damaged SOLUTION Replace the transmitt...

Страница 24: ...ement board fuse 2 A 5 x 20 Replacement motor fuse 10 A 5 x 20 Remote control battery Depends on model either 4LR44 6V or CR2025 3V Gate stops optional but recommended Gate solenoid lock optional but...

Страница 25: ...ing to which the Unit is attached G Faulty or at batteries in the remote control transmitter H Where the defect is due to conditions other than normal domestic use or dirt misuse neglect re accident e...

Страница 26: ...es or phone Merlin toll free New Zealand Auckland phone 09 415 4393 Phone toll free 0800 653 667 or 0800 MERLIN Fax toll free 0800 653 663 Australia NSW Vic Qld WA Phone toll free 1 800 638 234 Fax to...

Страница 27: ...5 sec 0 1 sec delay 2 5 sec delay DEL leaf closing delay 3 to 60 sec 3 sec close delay 30 sec close delay STRIKE delay open 1 sec TEST delay all 0 2 sec RESET 1 flash G815D 2 flashes G950 G915D red P2...

Страница 28: ...OFF cw OFF Force speed voltage 50 100 cw max STRIKE jumper ON OFF TEST jumper ON OFF Gates New or existing Leaf width x height Construction type coverage Load measured at gate bracket without opener c...

Отзывы: