DS1/T1 CPE loopback jack
555-233-116
156
Issue 4 October 2002
Configurations using fiber multiplexers
Use the loopback jack when customer premises DS1 wiring connects to an on-site
fiber multiplexer (MUX) and allows wiring to the network interface point on the
MUX to be remotely tested. For a G700 Media Gateway, this requires that the
MM710 CSU be set so it can be used on DS1 wiring to the MUX.
Fiber MUXs can take the place of Interface termination feeds as shown in
Figure 24
through
Figure 31
. Test these spans using the same procedures as
metallic spans. Note the following points:
1. Fiber MUXs may have loopback capabilities that can the service provider
can activate from the CO end. These may loop the signal back to the CO or
back to the DS1 board. If the MUX provides the equivalent of a line
loopback on the “problem” DS1 facility, activate it after a successful
loopback jack test, and use it to isolate problems to the wiring between the
loopback jack and the MUX.
2. Be aware that there are installations that use repeatered metallic lines
between the MUX and the “dumb” block. These lines require DC power for
the repeaters and this DC power is present at the “dumb” block interface to
the CPE equipment. A loopback jack is required in this configuration to
properly isolate and terminate the DC power.
To check for the presence of DC, make the following 4 measurements at the
network interface jack:
1. From transmit tip (T, Pin 5) to receive tip (T1, Pin 2)
2. From transmit ring (R, Pin 4) to receive ring (R1, Pin 1)
3. From transmit tip (T, Pin 5) to transmit ring (R, Pin 4)
4. From receive tip (T1, Pin 2) to receive ring (R1, Pin 1)
All measurements should read 0 (zero) volts DC. For pin numbers and pin
designations, refer to Integrated Channel Service Unit (ICSU) Installation and
Operation.
Содержание MultiVantage
Страница 6: ......
Страница 14: ...Contents 555 233 116 14 Issue 4 October 2002 A Connector and cable pinout charts 231 IN Index 243...
Страница 24: ...About this book 555 233 116 24 Issue 4 October 2002...
Страница 120: ...DEFINITY LAN gateway system 555 233 116 120 Issue 4 October 2002...
Страница 134: ...Terminal server installation 555 233 116 134 Issue 4 October 2002...
Страница 162: ...ISDN converters and adapters 555 233 116 162 Issue 4 October 2002...
Страница 172: ...Busy tone disconnect equipment for non U S installations 555 233 116 172 Issue 4 October 2002...
Страница 178: ...Call detail recording CDR option settings 555 233 116 178 Issue 4 October 2002...
Страница 188: ...DEFINITY INADS 555 233 116 188 Issue 4 October 2002...
Страница 196: ...Music on hold 555 233 116 196 Issue 4 October 2002...
Страница 224: ...Multimedia communications products MMCX MMCH ESM 555 233 116 224 Issue 4 October 2002...
Страница 242: ...Connector and Cable Pinout Charts 555 233 116 242 Issue 4 October 2002...