5. Drive by PC
43
© Copyright Reserved Autonics Co., Ltd.
⑩
Configuration of file management and communication
The file menu has the functions as listed in the table below. The data to be transmitted are the setting
value of the parameter/mode screen and the program of the program edit screen� The data transmission
from the main body can be sent all data together or some data�
File menu
Function
Operations
Open
Read a file
Data is read from a file on a disk.
The data opened is, also, written to the main body in On-line�
The extension name of the data file is *.nvd.
Save
Save a file
Data is stored in a disk along with its file name.
The extension name of the data file is *.nvd.
Upload
Read from
PMC-1HS/PMC-2HS
Data is read from the main body�
All All data
Program-All All programs
Program-X-axis Program data on X-axis
Program-Y-axis Program data on Y-axis
Parameter-All All parameter/mode
Parameter-X-axis Parameter/mode on X-axis
Parameter-Y-axis Parameter/mode on Y-axis
Caution
When starting operation program by online, it is uploaded
automatically�
Download
Add to
PMC-1HS/PMC-2HS
Data is added to the main body�
All All data
Program-All All programs
Program-X-axis Program data on X-axis
Program-Y-axis Program data on Y-axis
Parameter-All All parameter/mode
Parameter-X-axis Parameter/mode on X-axis
Parameter-Y-axis Parameter/mode on Y-axis
Caution
If data is added or changed on the parameter/mode screen or
the program edit screen in on-line, the data is automatically
added to the main body�
In the Option menu, you can mark serial communication port and select communication speed�
The serial communication port that your PC can use is displayed in COM port numbers.
For communication, the COM port must be marked.
In USB communication, if you select "My Computer → Properties (click your right mouse button) →
Hardware → Device Manager", you can check the COM port to be allocated next to "Prolific USB-to-
Serial Comm Port" in Port (COM and LPT).
The communication speed has the range from 9,600 to 115,200 bps� The Factory default is 9,600bps�
Faster communication speed makes faster response of the main body but is subject to receive the
influence of noise.
The Help menu indicates the version of the main body or the operation program� The top end and the
bottom end indicate the versions of the main body and the operation program respectively (Version:
******* and Version of app: *******).
⑪
Main body reset
This function is used to reset PMC-1HS/PMC-2HS main body.