5.
Hold lower indicator disc in position and turn upper disc with symbol
(OPEN)
until it is in alignment with the mark on the cover.
6.
Move valve to end position CLOSED again.
7.
Check settings:
If the symbol
(CLOSED) is no longer in alignment with mark on the cover:
7.1 Repeat setting procedure.
7.2 Check whether the appropriate reduction gearing has been selected, if
required.
71
SAEx 07.2 – SAEx 16.2/SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive Profinet
Commissioning (optional equipment settings)