Figure 26: Disassembly of mounting frame
[1]
Screws
[2]
Mounting frame with connection board
1.
Loosen screws [1] and remove mounting frame [2].
How to proceed
2.
Remove cable sheathing in a length of 250 – 300 mm.
3.
Insert the wires into the cable glands.
4.
Fasten cable glands with the specified torque to ensure required enclosure
protection.
Information: For shielded cables: Link the cable shield end via the cable gland
to the housing (earthing).
5.
Strip wires:
5.1 Remove wire sheathing of control cables (1...50) in a length of approx. 10
mm
5.2 Remove wire sheathing of motor cables (U,V,W) in a length of approx.
12 mm
6.
For flexible cables: Use wire end sleeves according to DIN 46228. For spring
clamp terminals, connection is also possible without wire end sleeves.
Information: For two flexible wires per terminal, a joint wire end sleeve must
be used (twin wire end sleeve).
32
SAEx 07.2 – SAEx 16.2/SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Electrical connection
ACExC 01.2 Intrusive Profinet