6.
Press
Edit
.
➥
Display indicates:
▶ Specialist (4)
User login
7.
Use
Up ▲ Down ▼
to select user:
Information: Required user level:
Specialist (4)
or higher
➥
The symbols have the following meaning:
-
black triangle:
▶
= current setting
-
white triangle:
▷
= selection (not saved yet)
8.
Press
Ok
.
➥
Display indicates:
Password 0***
9.
Enter password (
→
enter password).
➥
The screen indicates the pre-set type of seating (
▶Limit
or
▶Torque
) by means
of a black triangle
▶
.
Change settings
10. Use
Up ▲ Down ▼
to select new setting.
➥
The symbols have the following meaning:
-
black triangle:
▶
= current setting
-
white triangle:
▷
= selection (not saved yet)
11. Confirm selection via
Save
.
➥
The setting for the type of seating is complete.
12. Back to step 4 (CLOSED or OPEN): Press
Esc
.
10.2.
Open switch compartment
The switch compartment must be opened to perform the following settings.
Ignition of potentially explosive atmospheres caused by sparks!
Risk of death or serious injury!
→
Before opening the flameproof enclosure, ensure absence of gas and voltage.
→
Handle cover and housing parts with care.
→
Flameproof joints must neither be damaged nor soiled in any way.
→
Do not jam cover during fitting.
1.
Loosen screws [2] and remove cover [1] from the switch compartment.
58
SAEx 07.2 – SAEx 16.2/SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Commissioning (basic settings)
ACExC 01.2 Intrusive Profinet