![AUMA ACExC 01.2 Intrusive Скачать руководство пользователя страница 35](http://html1.mh-extra.com/html/auma/acexc-01-2-intrusive/acexc-01-2-intrusive_operation-instructions-manual_3016435035.webp)
6.2.3.
Profinet cables: connect
Figure 29: Profinet connection board with connection terminals
n–1
Profinet cable from previous device
n+1
Profinet cable to next device
(For line topology or redundant ring/MRP - Media Redundancy Protocol)
Profinet connection is made individually by means of a safe Ethernet-capable
insulation displacement connection. The colour coding of connection terminals are
matching the Ethernet cable according to Profinet (white/blue/yellow/orange).
Table 21: Connecting data
0.2 mm² – 0.34 mm² / AWG 24 – AWG 22
Connection capacity (solid wire)
0.2 mm² – 0.34 mm² / AWG 24 – AWG 22
Connection capacity (stranded)
1.
Remove cable sheathing and clamp shield under strain relief.
2.
Connect cables to connection terminals. For this, use a small screwdriver to lift
or push down the levers.
Table 22:
Connection terminal assignment
Colour of wire insulation
Function
Signal
Yellow
Transmit Data +
TD +
Orange
Transmit Data –
TD –
White
Receive Data +
RD +
Blue
Receive Data –
RD –
35
SAEx 07.2 – SAEx 16.2/SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive Profinet
Electrical connection