AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit
102
Elbow and Oil loop conversion tablet
Type
Pipe Dia.(mm)
Bend
Oil Loop
6.35
0.10
0.7
9.52
0.18
1.3
12.70
0.20
1.5
15.88
0.25
2.0
19.05
0.35
2.4
22.02
0.40
3.0
Equivalent pipe length L
=
Actual Pipe length L+ Bend Qty× Equivalent pipe bend Oil Loop Qty ×
Equivalent Oil Loop length
Sample:
ALCA-H42A5/C5 Actual Pipe length is 25 meters, Gas pipe diameter is 19.05mm. If there’s 5 bends and
2 oil loops during the installation, then the equivalent pipe length should be:
L=25+0.35×5+2.4×2=31.5(m)
◇
Specification of connection pipe for indoor unit and outdoor unit
Cooling Capacity(Btu/h)
18000
24000
36000
48000
60000
Connection
Pipe (mm)
Liquid Pipe
Φ6.35
Φ9.52
Φ9.52
Gas Pipe
Φ12.7
Φ15.88
Φ19.05
Max.
Length(m)
Liquid Pipe Dia.
Φ6.35
Φ9.52
Φ9.52
Gas Pipe Dia.
Φ12.7
Φ15.88
Φ19.05
Max. Length
20
30
50
Max. Height (m)
15
20
30
Max. Bend Qty
5
8
10
Emptying or vacuum
Before charging the refrigerant to the system, to ensure that there is no impurities, water or
non-condensable gas. So, emptying and vacuum operation should be carried out.
◇
Vacuum: when process this operation please be sure that the connection pipe is tightened up.
1. Screw off the cover of maintenance valve connection, connect the pressure gauge to the connection
of maintenance valve
2. Connect the vacuum pump to the pressure gauge, turn on the vacuum pump and pressure gauge to
process the vacuum operation toward the indoor unit and piping, while to ensure that the absolute
pressure is no less than 50Pa after this operation.
3. Turn off the pressure gauge and vacuum pump to keep the pressure in the same level in 20 minutes.
◇
Emptying: when process this operation, please disconnect the high pressure valve with liquid valve.
1. Connect the gas valve of the stop valve to the thimble side of the rubber hoses, the other side of
rubber hoses should be connected to the refrigerant tank.
2. Open the refrigerant tank valve, using the refrigerant inside the tank with high speed to empty the air
in the indoor unit and the connection piping. When the outlet air becomes mist (it feels cold by
touching it), then the air is emptied.
3. When ensure that the air is emptied, connect and tighten the high pressure valve of outdoor unit stop
valve and liquid side connection pipe, keep this state more than 10 seconds.
4. Use soapy what to test each connection junctions (including lengthen piping welding junction)
5. Confirmed that there is no leakage, turn off the valve of refrigerant tank, take down the rubber hose
as well.
◇
Turn on the high-low pressure valve of the outdoor unit.
After vacuum and emptying, screw back the cover of the maintenance valve of outdoor unit low pressure
valve, screw off the high-low pressure valve of the outdoor unit (note: shall totally turned off ). Connect
the refrigerant to the system.
Содержание AL-H18/4DR1(U)
Страница 1: ...AUKS DC Inverter 1 Drive1 50HZ R410A 1 Service manual DC Inverter 1 Drive 1 50Hz R410a...
Страница 3: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 3 Part 1 General description 1 Nomenclature...
Страница 5: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 5...
Страница 7: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 7...
Страница 21: ...AUKS DC Inverter 1 Drive1 50HZ R410A Four way cassette 21 Introduction of control board socket...
Страница 46: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling Floor Type 46 Introduction of control board socket...
Страница 55: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling Floor Type 55...
Страница 68: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit 68 Introduction of control board socket...
Страница 69: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit 69 6 Fan Performance ALMD H18 4DR1 ALMD H24 4DR1...
Страница 70: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit 70 ALMD H36 4DR1 ALMD H48 5DR1 ALMD H60 5DR1...
Страница 89: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 89 AL H48 5DR1 U AL H60 5DR1 U...
Страница 92: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 92 Filter board...
Страница 109: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 109...
Страница 120: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 120 Communication failure between indoor and outdoor unit...
Страница 121: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 121 Outdoor protection phase sequence...
Страница 122: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 122 Cooling high pressure protection...
Страница 123: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 123 Heating high pressure protection...
Страница 124: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 124 Cooling low pressure protection...
Страница 125: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 125 Heating low pressure protection...
Страница 126: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 126 Cooling exhaust temperature protection...
Страница 127: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 127 Heating exhaust temperature protection...
Страница 128: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 128 Refrigerant shortage or four way valve failure protection...
Страница 129: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 129 Sensor failure protection...
Страница 131: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 131 Poor effect...
Страница 132: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 132...
Страница 133: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 133 Abnormal sound or viberation...
Страница 134: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 134...
Страница 135: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 135 Abnormal odor...
Страница 136: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 136 Air switch action when air conditioner starting up...
Страница 137: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 137 Air conditioner water leakage...
Страница 147: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 147 Wired controller XK 05...
Страница 148: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 148...
Страница 149: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 149 Installation of wired controller...