AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit
104
Additional refrigerant charge
When pipe length exceeds 5m, please add refrigerant according to the table below:
Connection piping
Piping size)
Additional refrigerant charge
amount (kg/m)
Gas pipe
Liquid pipe
Piping between
indoor and outdoor
unit
φ9.52×0.75mm
φ6.35×0.75mm
0.02
φ12.7×1mm
φ6.35×0.75mm
0.02
φ15.88×1mm
φ9.52×0.75mm
0.05
φ19.05×1mm
φ9.52×0.75mm
0.07
φ19.05×1mm
φ12.7×1mm
0.09
Oil grade and standard oil-filled volume of Compressor
Outdoor unit model
Brand
Compressor model
Oil type
Oil volume(cm
3
)
AL-H18/4DR1(U)
Shanghai
Hitachi
ATD141RDPA8JT
68HES-H
480
AL-H24/4DR1(U)
Shanghai
Hitachi
ATL232UDPC9AU
68HES-H
630
AL-H36/4DR1(U)
GMCC
DA250S2C-30MT
VG74
820
AL-H48/5DR1(U)
GMCC
ATQ420D2UMU
VG74
1400
AL-H60/5DR1(U)
GMCC
ATQ420D2UMU
VG74
1400
Others
Users to install the air conditioner at site shall ensure that the oil can return to the unit smoothly.
◇
Horizontal pipes should incline toward the outdoor unit using a 20:1 slop.e
◇
If there is a height difference between the indoor and outdoor unit, oil loops should be installed in the inter
connecting gas (large) pipe;
When the vertical pipe height difference is less than 5 meters, an oil loop should be installed at the bottom of
the gas (large) pipe;
When the vertical pipe height difference is more than 5 meters, then for every 5 meters an oil loop must be
installed at the bottom of the gas (large) pipe, and a short loop (liquid ring) should be installed at the exit of the
indoor unit liquid (small) pipe;
When the connecting gas pipe vertical height difference is less than 5 meters but the constant rise distance is
too long, an oil loop should be installed in the gas (large) pipe every 10 meters.
◇
When the outdoor and indoor units are at the same elevation, the oil deposit bend and liquid ring do not
need to be installed, if the horizontal connecting pipe length is less than 10 meters.
When the horizontal connecting pipe length is more than 10 metres, install an oil loop in the gas (large) pipe
every 10 metres.
Содержание AL-H18/4DR1(U)
Страница 1: ...AUKS DC Inverter 1 Drive1 50HZ R410A 1 Service manual DC Inverter 1 Drive 1 50Hz R410a...
Страница 3: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 3 Part 1 General description 1 Nomenclature...
Страница 5: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 5...
Страница 7: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 7...
Страница 21: ...AUKS DC Inverter 1 Drive1 50HZ R410A Four way cassette 21 Introduction of control board socket...
Страница 46: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling Floor Type 46 Introduction of control board socket...
Страница 55: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling Floor Type 55...
Страница 68: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit 68 Introduction of control board socket...
Страница 69: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit 69 6 Fan Performance ALMD H18 4DR1 ALMD H24 4DR1...
Страница 70: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit 70 ALMD H36 4DR1 ALMD H48 5DR1 ALMD H60 5DR1...
Страница 89: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 89 AL H48 5DR1 U AL H60 5DR1 U...
Страница 92: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 92 Filter board...
Страница 109: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 109...
Страница 120: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 120 Communication failure between indoor and outdoor unit...
Страница 121: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 121 Outdoor protection phase sequence...
Страница 122: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 122 Cooling high pressure protection...
Страница 123: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 123 Heating high pressure protection...
Страница 124: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 124 Cooling low pressure protection...
Страница 125: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 125 Heating low pressure protection...
Страница 126: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 126 Cooling exhaust temperature protection...
Страница 127: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 127 Heating exhaust temperature protection...
Страница 128: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 128 Refrigerant shortage or four way valve failure protection...
Страница 129: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 129 Sensor failure protection...
Страница 131: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 131 Poor effect...
Страница 132: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 132...
Страница 133: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 133 Abnormal sound or viberation...
Страница 134: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 134...
Страница 135: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 135 Abnormal odor...
Страница 136: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 136 Air switch action when air conditioner starting up...
Страница 137: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 137 Air conditioner water leakage...
Страница 147: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 147 Wired controller XK 05...
Страница 148: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 148...
Страница 149: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 149 Installation of wired controller...