AUKS DC Inverter 1 Drive1 50HZ R410A Controller
152
2)
Setting of Indoor Model Based on Wired remote Controller
(1).Press [Filter Net Button] for 5 seconds, Indoor number “01” will be displayed in temperature zone of LCD
screen and “0101” will be displayed in timing setting zone of LCD screen.
“01” means that indoor unit is 01; “0101” means this parameter number is 01 and the parameter value is 01.
(2).Press [+/- Button of Clock], the parameter No. and value “0201”, “0301”, “0401” will be displayed
successively. See the table below for number of parameters and corresponding value meaning.
(3).Then press [Mode Button] once, “corresponding parameter value 01” will flicker; press [+/-button of time] to
change the value into “05”, press [Mode Button] to confirm. This parameter is changed to 05.
If there is no operation for 15 seconds, then automatically exit and keep the previous setting.
3)
Setting of Indoor Model Based on Wired remote Controller
Indoor Model
Type setting
【
04
】
Capacity setting
【
05
】
Duct Type
ALMD-H18/4DR1
12
18
ALMD-H24/4DR1
12
23
ALMD-H36/4DR1
12
36
ALMD-H48/5DR1
12
50
ALMD-H60/5DR1
12
60
4-way
Cassette
ALCA-H18/4DR1
10
18
ALCA-H24/4DR1
11
23
ALCA-H36/4DR1
11
36
ALCA-H48/5DR1
11
50
ALCA-H60/5DR1
11
60
Ceiling floor
ALCF-H18/4DR1
13
18
ALCF-H24/4DR1
13
23
ALCF-H36/4DR1
13
36
ALCF-H48/5DR1
13
50
ALCF-H60/5DR1
13
60
Indoor NO.
Parameter NO.
Clock +/- button
Corresponding
parameter value
Filter Net button
Temp +/- button
Mode button
Содержание AL-H18/4DR1(U)
Страница 1: ...AUKS DC Inverter 1 Drive1 50HZ R410A 1 Service manual DC Inverter 1 Drive 1 50Hz R410a...
Страница 3: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 3 Part 1 General description 1 Nomenclature...
Страница 5: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 5...
Страница 7: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 7...
Страница 21: ...AUKS DC Inverter 1 Drive1 50HZ R410A Four way cassette 21 Introduction of control board socket...
Страница 46: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling Floor Type 46 Introduction of control board socket...
Страница 55: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling Floor Type 55...
Страница 68: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit 68 Introduction of control board socket...
Страница 69: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit 69 6 Fan Performance ALMD H18 4DR1 ALMD H24 4DR1...
Страница 70: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit 70 ALMD H36 4DR1 ALMD H48 5DR1 ALMD H60 5DR1...
Страница 89: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 89 AL H48 5DR1 U AL H60 5DR1 U...
Страница 92: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 92 Filter board...
Страница 109: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 109...
Страница 120: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 120 Communication failure between indoor and outdoor unit...
Страница 121: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 121 Outdoor protection phase sequence...
Страница 122: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 122 Cooling high pressure protection...
Страница 123: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 123 Heating high pressure protection...
Страница 124: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 124 Cooling low pressure protection...
Страница 125: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 125 Heating low pressure protection...
Страница 126: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 126 Cooling exhaust temperature protection...
Страница 127: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 127 Heating exhaust temperature protection...
Страница 128: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 128 Refrigerant shortage or four way valve failure protection...
Страница 129: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 129 Sensor failure protection...
Страница 131: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 131 Poor effect...
Страница 132: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 132...
Страница 133: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 133 Abnormal sound or viberation...
Страница 134: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 134...
Страница 135: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 135 Abnormal odor...
Страница 136: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 136 Air switch action when air conditioner starting up...
Страница 137: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 137 Air conditioner water leakage...
Страница 147: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 147 Wired controller XK 05...
Страница 148: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 148...
Страница 149: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 149 Installation of wired controller...