AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit
64
Equivalent Pipe length L
=
Actual Pipe length L+ Bend Qty× Equivalent pipe bend Oil Loop Qty ×
Equivalent Oil Loop length
Sample:
ALCA-H48/5 Actual Pipe length is 25 meters, Gas pipe diameter is 19.05mm. If there’s 5 bends and 2 oil
loops during the installation, then the equivalent pipe length should be:
L=25+0.35×5+2.4×2=31.5(m)
◇
Specification of Connection Pipe for Indoor Unit and Outdoor Unit
Cooling Capacity(Btu/h)
18000
24000
36000
48000
60000
Connection Pipe
(mm)
Liquid Pipe
Φ6.35
Φ9.52
Φ9.52
Gas Pipe
Φ12.7
Φ15.88
Φ19.05
Max. Length
20
30
30
50
Max. Height (m)
15
15
20
30
Max. Bend Qty
5
8
8
10
Extra R410a per meter when the pipe
length is more than 5 meter (kg)
0.02
0.02
0.05
0.07
Caution:
1. The standard Pipe length is 5m, if the pipe length is less than this then no additional charging is
necessary. If the pipe length is more than this then you should charge more refrigerant into the
system according to the above Charging Data
2. The thickness of the pipe is 0.6-1.0, bearing pressure is 4.2MPa;
3. If the connection pipe is too long, the cooling capacity and stability would be decreased. And the more
bend quantity, the resistance in the piping system would be bigger, then the cooling and heating
capacity would be decreased even lead to compressor broken. We suggest you to use the shortest
connection pipe according to the pipe length parameter in this manual. If the height difference
between outdoor and indoor unit is more than 5m, an oil trap should be installed in the gas pipe for
every 10 meters.
Содержание AL-H18/4DR1(U)
Страница 1: ...AUKS DC Inverter 1 Drive1 50HZ R410A 1 Service manual DC Inverter 1 Drive 1 50Hz R410a...
Страница 3: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 3 Part 1 General description 1 Nomenclature...
Страница 5: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 5...
Страница 7: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 7...
Страница 21: ...AUKS DC Inverter 1 Drive1 50HZ R410A Four way cassette 21 Introduction of control board socket...
Страница 46: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling Floor Type 46 Introduction of control board socket...
Страница 55: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling Floor Type 55...
Страница 68: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit 68 Introduction of control board socket...
Страница 69: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit 69 6 Fan Performance ALMD H18 4DR1 ALMD H24 4DR1...
Страница 70: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit 70 ALMD H36 4DR1 ALMD H48 5DR1 ALMD H60 5DR1...
Страница 89: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 89 AL H48 5DR1 U AL H60 5DR1 U...
Страница 92: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 92 Filter board...
Страница 109: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 109...
Страница 120: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 120 Communication failure between indoor and outdoor unit...
Страница 121: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 121 Outdoor protection phase sequence...
Страница 122: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 122 Cooling high pressure protection...
Страница 123: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 123 Heating high pressure protection...
Страница 124: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 124 Cooling low pressure protection...
Страница 125: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 125 Heating low pressure protection...
Страница 126: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 126 Cooling exhaust temperature protection...
Страница 127: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 127 Heating exhaust temperature protection...
Страница 128: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 128 Refrigerant shortage or four way valve failure protection...
Страница 129: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 129 Sensor failure protection...
Страница 131: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 131 Poor effect...
Страница 132: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 132...
Страница 133: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 133 Abnormal sound or viberation...
Страница 134: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 134...
Страница 135: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 135 Abnormal odor...
Страница 136: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 136 Air switch action when air conditioner starting up...
Страница 137: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 137 Air conditioner water leakage...
Страница 147: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 147 Wired controller XK 05...
Страница 148: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 148...
Страница 149: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 149 Installation of wired controller...