7.6 Duct pipeline installation
◇
Using canvas to connect between indoor unit and duct pipeline, in order to save unnecessary vibration,
as to the detail connection method please refer to the following picture.
7.7 Drainage pipe
◇
Drainage pipes must be wrapped with heat insulation materials, otherwise it will cause frost or droplets,
see picture as follows:
Heat insulation material: rubber insulation pipe with the thickness of more than 8mm
◇
Drainage pipe must have a downward gradient (1 / 50 1 / 100).If the drain pipe is installed ups and
downs, it will cause water backflow or leakage etc.
◇
When finish installation please carry out the drainage test to ensure that the water flow through the
pipeline fluently, and carefully observe the junction to ensure that there is no water leakage at the
junction. If the unit is installed in the newly built house, strongly recommend that this test taken before
the CFiling installation. Even it is the heating only unit, this test is unavoidable.
7.8 Remote controller receiver
◇
Installation site: recommend that the receiver is mounted with the distance of 30~50 cm to the indoor
unit air outlet(on your choice as well), while must ensure that the receiver can get the signal that the
remote controller sends, please refer to the following installation picture:
Содержание AL-H18/4DR1(U)
Страница 1: ...AUKS DC Inverter 1 Drive1 50HZ R410A 1 Service manual DC Inverter 1 Drive 1 50Hz R410a...
Страница 3: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 3 Part 1 General description 1 Nomenclature...
Страница 5: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 5...
Страница 7: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 7...
Страница 21: ...AUKS DC Inverter 1 Drive1 50HZ R410A Four way cassette 21 Introduction of control board socket...
Страница 46: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling Floor Type 46 Introduction of control board socket...
Страница 55: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling Floor Type 55...
Страница 68: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit 68 Introduction of control board socket...
Страница 69: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit 69 6 Fan Performance ALMD H18 4DR1 ALMD H24 4DR1...
Страница 70: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ducted type Indoor unit 70 ALMD H36 4DR1 ALMD H48 5DR1 ALMD H60 5DR1...
Страница 89: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 89 AL H48 5DR1 U AL H60 5DR1 U...
Страница 92: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 92 Filter board...
Страница 109: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 109...
Страница 120: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 120 Communication failure between indoor and outdoor unit...
Страница 121: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 121 Outdoor protection phase sequence...
Страница 122: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 122 Cooling high pressure protection...
Страница 123: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 123 Heating high pressure protection...
Страница 124: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 124 Cooling low pressure protection...
Страница 125: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 125 Heating low pressure protection...
Страница 126: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 126 Cooling exhaust temperature protection...
Страница 127: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 127 Heating exhaust temperature protection...
Страница 128: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 128 Refrigerant shortage or four way valve failure protection...
Страница 129: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 129 Sensor failure protection...
Страница 131: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 131 Poor effect...
Страница 132: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 132...
Страница 133: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 133 Abnormal sound or viberation...
Страница 134: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 134...
Страница 135: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 135 Abnormal odor...
Страница 136: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 136 Air switch action when air conditioner starting up...
Страница 137: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 137 Air conditioner water leakage...
Страница 147: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 147 Wired controller XK 05...
Страница 148: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 148...
Страница 149: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 149 Installation of wired controller...