Installation & Servicing instructions ATAG iC-Range
25
Terminal position
Min. distance (mm)
A
Directly below an opening, air brick, windows, etc.
300 (See Note 1)
B
Below gutters, soil pipes or drain pipes
75 (See Note 3)
C
Below eaves
200 (See Note 3)
D
Below balconies
200 (See Note 3)
E
From a vertical drain pipe or soil pipe
150 (See Note 3)
F
From an internal or external corner
300 (See Note 2)
G
Above ground, roof or balcony level
300
H
From a surface or boundary facing the terminal
600 (See Note 4)
I
From a terminal facing the terminal
1200
J
Above an opening, air brick, window etc.
300 (See Note 1)
K
Vertically from a terminal on the same wall
1500
L
Horizontally from a terminal on the same wall
300
M
Horizontally from an opening, air brick, window etc.
300 (See Note 1)
N
Minimum protrusion through a roof
300
O
From a vertical obstruction
300
P
From an openable window
600
Q
From an adjacent vertical terminal
600
R
From an opening in the car port (e.g. door, window) into the dwelling
1200
S
Below a roof window
2000
T
Terminal parallel to a boundary
300
Notes:
1.
In addition, the terminal should not be nearer than 150mm to the framework of an opening into the building, i.e. a window surround or door surround.
2.
This clearance may be reduced to 25mm without eff ecting the performance of the boiler. However, to ensure the condensate plume does not aff ect adjacent
surfaces a clearance of 300mm is preferable.
3.
These clearances may be reduced to 25mm without eff ecting the performance of the boiler. However, to ensure the condensate plume does not aff ect adjacent
surfaces the terminal can be extended beyond gutters, pipes, eaves, balconies etc.
4.
To reduce the possibility of nuisance to neighbouring buildings etc. it is recommended the terminal should not be less than 2500mm from car parking spaces,
building boundary walls, fences etc.
5.
A terminal must not be sited under a car port roof.
6.
In certain weather conditions the terminal will emit a plume of steam. If possible avoid positioning the terminal where this may cause a nuisance, i.e. positions A,
D, G, H, J or M.
7.
The fl ue terminal must be exposed to the external air and the position must allow the free passage of air across it at all times.
8.
A terminal must not be sited below 2m where people have access to, such as public footpaths, access routes, patios etc. However, If the terminal is fi tted less
than 2m above a surface where there is no public access, the terminal must be protected by a terminal guard.
Figure 9.8.1.c
Содержание iC 24
Страница 33: ...Installation Servicing instructions ATAG iC Range 33 Figure 10 7 a 10 9 Electrical diagram...
Страница 56: ...Installation Servicing instructions ATAG iC Range 56 Annex C Short parts list...
Страница 57: ...Installation Servicing instructions ATAG iC Range 57...
Страница 58: ......
Страница 59: ......
Страница 60: ......
Страница 61: ......